Table 10 . Function codes (continued)
Parameter
Unit of
Measure
Security Level
Default Value
Key Entry Limit
To Read
To Write
To Reset
Low
High
845 2179 User Map
Selection
CL-7 Default Event
---
View
Modify
NA
CL-7
Default
NA
NA
•The selection of the active 2179 protocol map for Com 2. The available options are: User
1; User 2; CL-7 Default; CL-7 Default Events; CL-7 Advanced; CL-6 Default; CL-6 Default
Events; CL-7 3Ph Default; CL-7 3Ph Default Evt; CL-7 3Ph Advanced.
845 2179 Dead Sync
Timeout
10 Msec
Msec
View
Admin
NA
10
1
1000
•A period of time during which the received data line is idle, defining the end of the
previous message. This idle time is the dead-line sync period. The control is now
synchronized so that the next byte received is considered the beginning of a new message.
This parameter is for Com 2.
845 2179 Master Time
Format
Local
NA
View
Modify
NA
Local
NA
NA
•This selects the master time format for use with the 2179 protocol. This parameter is for
Com 2.
•Options include: Local; UTC.
846 Modbus Device
Address
XXX
---
View
Modify
NA
1
1
247
•Specifies the address from 1 to 247, of the RTU instance on the control for Com 2.
•Configuration parameters for Modbus are displayed when protocol is available.
846 Modbus User Map
Selection
CL-7 Default
---
View
Modify
NA
CL-7
Default
NA
NA
•The selection of the active Modbus protocol map for Com 2. The available options are:
User 1; User 2; CL-7 Default; CL-7 Default Events; CL-7 Advanced; CL-6 Default; CL-6
Default Events; CL-7 3Ph Default; CL-7 3Ph Default Evt; CL-7 3Ph Advanced.
846 Modbus Listening
Port Number
XXXXX
---
View
Modify
NA
502
1
65534
•This defines the IP port number that will be monitored for incoming MODBUS TCP
connections.
860 LoopShare Comms
State
Active
---
View
NA
NA
NA
NA
NA
•This is the state of LoopShare Communications. It will display either Active or Inactive.
861 LoopShare Comm
Table Assignment
Passive
---
View
Modify
NA
Passive
NA
NA
•This is the device in the LoopShare Table. The options include: VR1; VR2; VR3; Passive.
862 LoopShare Comm
Tx Delay
XXXXX mSec
MilliSec
View
Modify
NA
0
0
10000
•This is the delay between the time a device receives an updated LFDT and when the device
passes it along.
863 LoopShare Comm
Timeout
XX Seconds
Seconds
View
Modify
NA
3
1
60
•This is the LoopShare communications timeout time.
116
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS
MN225003EN April 2018
CL-7 Voltage Regulator Control