Table 4 . Programming for reverse power and additional features
Function
code
Description
Instructions
141
Regulator Identification
FUNC, 141, ENTER, EDIT,
Value
, ENTER
Requirements for Reverse Sensing Mode without IDPTs
039
Source Voltage Calculation
FUNC, 39, ENTER, EDIT Scroll -
On
;
Off
, ENTER
Required for Reverse Sensing Modes
051
Reverse Set Voltage
FUNC, 51, ENTER, EDIT,
Value
, ENTER
052
Reverse Bandwidth
FUNC, 52, ENTER, EDIT,
Value
, ENTER
053
Reverse Time Delay
FUNC, 53, ENTER, EDIT,
Value
, ENTER
054
Reverse Line Drop Comp. Resistance
FUNC, 54, ENTER, EDIT,
Value
, ENTER
055
Reverse Line Drop Comp. Reactance
FUNC, 55, ENTER, EDIT,
Value
, ENTER
056
Reverse Sensing Mode
FUNC, 56, ENTER, EDIT, Scroll -
Locked Forward
;
Locked Reverse
;
Reverse Idle
;
Bi-directional; Neutral Idle; Co-generation; React Bi-directional, Bias Bi-directional,
Bias Co-generation; Reverse Co-generation,
ENTER
Required for Voltage Reduction Mode
070
Voltage Reduction Mode
FUNC, 70, ENTER, EDIT, Scroll -
Off
;
Local/Digital Remote
;
Remote/Latch
;
Remote/Pulse
,
ENTER
072
Local/Digital Reduction Value
FUNC, 72, ENTER, EDIT,
Value
, ENTER
073
Remote #1 Value
FUNC, 73, ENTER, EDIT,
Value
, ENTER
074
Remote #2 Value
FUNC, 74, ENTER, EDIT,
Value
, ENTER
075
Remote #3 Value
FUNC, 75, ENTER, EDIT,
Value
, ENTER
076
# of Pulse Reduction Steps
FUNC, 76, ENTER, EDIT,
Value
, ENTER
077
% of Voltage Red Per Pulse Step
FUNC, 77, ENTER, EDIT,
Value
, ENTER
Required for Voltage Limit Mode
080
Voltage Limit Mode
FUNC, 80, ENTER, EDIT, Scroll -
Off
;
High Limit Only
;
High/Low Limits
, IVVC High Limit Only,
IVVC High/Low Limit, ENTER
081
High Voltage Limit
FUNC, 81 ENTER, EDIT,
Value
, ENTER
082
Low Voltage Limit
FUNC, 82, ENTER, EDIT,
Value
, ENTER
Multi-phase programming
When programming a control for multi-phase operation,
there are a number of setting that configure the control
for operation and a number that configure the control
to function with the connected voltage regulators. It is
important to identify the pertinent settings applying to the
individual regulators and to the control and enter them
correctly. Refer to
Section 6: Control Features: Multi-
MZ225003EN
CL-7 Multi-phase Control Reference
for guidance on
programming the control for multi-phase operation.
All of the basic control and regulator operational information
in this manual applies to controls and regulators whether
they are in a single- or multi-phase configuration. When
in the multi-phase configuration, the multi-phase LEDs
(marked 1, 2 and 3), see
to which of the regulators the parameters apply. When
programming the multi-phase control, pay attention to the
LEDs to insure that the parameters are being entered for
the correct regulator. Pressing the forward arrow will cycle
the display through each of the connected regulators.