Step 6
Using supplied grounding clamps, connect bracket to
system ground. Grounding clamp accommodates wire
ranging from #8 sol to 2/0 str.
Attach drain wire of loadbreak connector (LCN) to system
ground.
Step 7
Remove protective shipping caps from 600 A deadbreak
bushing interfaces. Clean and lubricate.
Step 8
Install mating 600 A deadbreak terminations to each
deadbreak bushing per the instructions provided with those
kits.
Square bracket installation instructions
Step 1
Using 1/2" hardware (customer supplied) mount assembly
to mounting surface or mounting plates of enclosure. See
Figure 9.
ote:
N
The assembly should be secured with four (4) bolts
using one upper and lower slot on each side of the
bracket.
Step 2
Using supplied grounding clamps, connect bracket to
system ground. Grounding clamp accommodates wire
ranging from #8 sol to 2/0 str.
Attach drain wire of loadbreak connector (LCN) to system
ground.
Step 3
Remove protective shipping caps from 600 A loadbreak
bushing interfaces. Clean and lubricate.
Step 4
Install mating 600 A deadbreak terminations to each
deadbreak bushing per the instructions provided with those
kits.
12.0
.8
(20 mm)
2.0
(51 mm)
7.0
(178 mm)
7.0
(178 mm)
1.0
.530
(25 mm)
(13 mm)
(305 mm)
Figure 9. Square bracket dimensions.
4
CLEER LOADBREAK CONNECTOR SYSTEM INSTALLATION INSTRUCTIONS
MN650019EN March 2016