Eaton ConnectUPS Web/SNMP Card Quick Start Instructions 164950185—Rev D 5
Section 2
Install the Card
NOTE
The hot-swappable ConnectUPS Web/SNMP cards can be
installed without turning off the UPS or disconnecting the load.
NOTE
Two types of ConnectUPS Web/SNMP cards (X and BD) are
supported by PredictPulse.
To install a ConnectUPS Web/SNMP card:
1.
Make sure you have the correct dip switch position:
- If you are going to enter an IP address manually, verify that both DIP
switches on the card are set to the 0 or OFF position, which is flipped up
(see Figure 1 and Figure 2).
- If you are setting up the ConnectUPS Web/SNMP card in a DHCP
environment, set DIP switch 2 to the 1 or ON position, which is flipped
down.
2.
If not already done, record the MAC address from the label on the card for
future reference (see Step 2 in the “Installation Checklist”).
NOTE
If another card is already installed with an attached
communication cable, disconnect the cable and then remove
the card.
3.
To prevent electrostatic discharge (ESD), place one hand on a metal surface,
such as the UPS rear panel.
4.
Remove the blank communication bay cover from the UPS. Retain the
screws.
5.
Slide the card into the open slot and secure it with the screws removed in
Step 1 (see Figure 1 and Figure 2).
Figure 1. Installing the Card (UPS-X Card Shown)
COM
1
2
3
4
ConnectUPS-X Web/SNMP/xHub Card
RESET
100 10
POWER
STATUS
Uplink
COM
2
1
3
4
ON
1 2
Содержание ConnectUPS Web/SNMP Card
Страница 24: ...Eaton ConnectUPS Web SNMP Card Quick Start Instructions 164950185 Rev D 24 Figure 16 Example Completion E mail ...
Страница 25: ......
Страница 26: ...164950239 164940185 D ...