2.  Wire brush all terminals, connectors and electrical 

conductors.

3.  Apply an oxide inhibitor prior to making electrical 

connections.

4.  Insert Companion II fuse and conductors into 

connectors and tighten.

• 

Maintain a minimum of 14" of clearance from the 

source leads to the lower end of the Companion II 

fuse and related energized hardware of the cutout.

• 

When mounting the Companion II fuse in the upper 

terminal of a fused cutout, replace expendable caps 

with solid caps.

• 

Make sure vents from the cutout fuse holder will 

not direct expulsion gases towards the Companion 

II fuse.

• 

Apply minimal cantilever load to the Companion II 

fuse.

5.  Re-energize the line using approved safety procedures.

Figure 4.  Companion II fuse mounted from a bail 

attached to the overhead line.

ARRESTER

COMPANION II

FUSE

CUTOUT FUSE 

LINK IN FUSE-

HOLDER

TRANSFORMER

PRIMARY 

BUSHING

Figure 2.  Companion II fuse mounted on the source side of 

the cutout.

ARRESTER

COMPANION II

FUSE

CUTOUT FUSE 

LINK IN FUSE-

HOLDER

TRANSFORMER

PRIMARY 

BUSHING

Figure 3.

 

Companion II fuse mounted on the load side 

of the cutout.

ARRESTER

COMPANION II

FUSE

CUTOUT FUSE 

LINK IN FUSE-

HOLDER

TRANSFORMER

PRIMARY 

BUSHING

3

COMPANION II BACK-UP CURRENT-LIMITING FUSE INSTALLATION INSTRUCTIONS

    MN132009EN   

Содержание Companion II back-up current-limiting fuse

Страница 1: ...Companion II back up current limiting fuse installation instructions COOPER POWER SERIES Fusing Equipment MN132009EN Effective December 2015 Supersedes S240 64 1 December 2013...

Страница 2: ...ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES In n...

Страница 3: ...ial inspection 1 Handling and storage 1 Quality standards 1 APPLICATION Fuse application 2 INSTALLATION PROCEDURE Installation of the Companion II fuse 2 Installation of terminal options 4 RE FUSING R...

Страница 4: ...Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally approved safety procedures when working around hi...

Страница 5: ...actory It is in good condition when accepted by the carrier for shipment Upon receipt of the Companion II fuse inspect the connector thoroughly for damage and loss of parts incurred during shipment If...

Страница 6: ...of Terminal Options on page 4 1 Remove fuseholder from distribution cutout using a hookstick Always use a loadbreak device to open an energized cutout Follow manufacturer s recommendations for operati...

Страница 7: ...irect expulsion gases towards the Companion II fuse Apply minimal cantilever load to the Companion II fuse 5 Re energize the line using approved safety procedures Figure 4 Companion II fuse mounted fr...

Страница 8: ...ECT ARRESTER CUTOUT FUSE LINK IN FUSE HOLDER TRANSFORMER PRIMARY BUSHING Figure 6 Completely Self Protected CSP transformer mounted Companion II fuse without separate distribution cutout ARRESTER COMP...

Страница 9: ...5 ft lbs Figure 10 Spline stud terminal Terminal code G 1 Insert threaded end of the spline stud into the tapped center hole of the Companion II fuse and torque spline stud to 10 15 ft lbs Figure 11 O...

Страница 10: ...split lock washer onto the bolt and insert the bolt through the connector hole into the tapped center hole of the fuse and torque the bolt to 10 15 ft lbs Figure 15 3 Assemble carriage bolt parallel...

Страница 11: ...fuse should always be tested after an operation of the fuse cutout 1 Perform a continuity check on the Companion II fuse 2 If the Companion II fuse does have continuity go to the Installation Procedu...

Страница 12: ...nformation call 1 877 277 4636 or visit www eaton com cooperpowerseries Eaton 1000 Eaton Boulevard Cleveland OH 44122 United States Eaton com Eaton s Cooper Power Systems Division 2300 Badger Drive Wa...

Отзывы: