Introduction

Eaton's Cooper Power™ series Companion™ II fuse is 

a back-up cur rent-limiting fuse designed to be used in 

series with a distribution cutout or similar fuse capable 

of interrupting currents up to and including the minimum 

interrupting current of the Companion II fuse. The 

Companion II fuse limits the energy input during a high fault 

current condition.

Read this manual first

Read and understand the contents of this manual and follow 

all locally approved procedures and safety practices before 

installing or operating this equipment.

Additional information

These instructions cannot cover all details or variations 

in the equipment, procedures, or process described nor 

provide directions for meeting every possible contingency 

during installation, operation, or maintenance. When 

additional information is desired to satisfy a problem not 

covered sufficiently for the user's purpose, please contact 

your Eaton representative.

Acceptance and initial inspection

Each Companion II fuse is completely inspected and tested 

at the factory. It is in good condition when accepted by 

the carrier for shipment. Upon receipt of the Companion 

II fuse, inspect the connector thoroughly for damage and 

loss of parts incurred during shipment. If damage or loss is 

discovered, file a claim with the carrier immediately.

Handling and storage

If the Companion II fuse is to be stored for an appreciable 

time before installation, provide a clean, dry storage 

area. Locate the Companion II fuse so as to minimize the 

possibility of physical damage.

Quality standards

ISO 9001 Certified Quality Management System

EYEBOLT 

TERMINAL

COMPANION II 

FUSE BODY

SPLINE STUD 

TERMINAL

 CAUTION 

The Companion II fuse is designed to be installed in 

accordance with normal safe operating procedures. 

These instructions are not intended to supersede or 

replace existing safety and operating procedures. READ 

ALL THE INSTRUCTIONS BEFORE IN STALL ING THE 

COMPANION II DISTRIBUTION FUSE. The Companion II 

fuse should be installed and serviced only by personnel 

familiar with good safety practice and the handling of 

high-voltage electrical equipment.

Figure 1.  Companion II back-up current-limiting fuse with 

spline stud and eyebolt terminal options.

1

COMPANION II BACK-UP CURRENT-LIMITING FUSE INSTALLATION INSTRUCTIONS

    MN132009EN   

Содержание Companion II back-up current-limiting fuse

Страница 1: ...Companion II back up current limiting fuse installation instructions COOPER POWER SERIES Fusing Equipment MN132009EN Effective December 2015 Supersedes S240 64 1 December 2013...

Страница 2: ...ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES In n...

Страница 3: ...ial inspection 1 Handling and storage 1 Quality standards 1 APPLICATION Fuse application 2 INSTALLATION PROCEDURE Installation of the Companion II fuse 2 Installation of terminal options 4 RE FUSING R...

Страница 4: ...Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally approved safety procedures when working around hi...

Страница 5: ...actory It is in good condition when accepted by the carrier for shipment Upon receipt of the Companion II fuse inspect the connector thoroughly for damage and loss of parts incurred during shipment If...

Страница 6: ...of Terminal Options on page 4 1 Remove fuseholder from distribution cutout using a hookstick Always use a loadbreak device to open an energized cutout Follow manufacturer s recommendations for operati...

Страница 7: ...irect expulsion gases towards the Companion II fuse Apply minimal cantilever load to the Companion II fuse 5 Re energize the line using approved safety procedures Figure 4 Companion II fuse mounted fr...

Страница 8: ...ECT ARRESTER CUTOUT FUSE LINK IN FUSE HOLDER TRANSFORMER PRIMARY BUSHING Figure 6 Completely Self Protected CSP transformer mounted Companion II fuse without separate distribution cutout ARRESTER COMP...

Страница 9: ...5 ft lbs Figure 10 Spline stud terminal Terminal code G 1 Insert threaded end of the spline stud into the tapped center hole of the Companion II fuse and torque spline stud to 10 15 ft lbs Figure 11 O...

Страница 10: ...split lock washer onto the bolt and insert the bolt through the connector hole into the tapped center hole of the fuse and torque the bolt to 10 15 ft lbs Figure 15 3 Assemble carriage bolt parallel...

Страница 11: ...fuse should always be tested after an operation of the fuse cutout 1 Perform a continuity check on the Companion II fuse 2 If the Companion II fuse does have continuity go to the Installation Procedu...

Страница 12: ...nformation call 1 877 277 4636 or visit www eaton com cooperpowerseries Eaton 1000 Eaton Boulevard Cleveland OH 44122 United States Eaton com Eaton s Cooper Power Systems Division 2300 Badger Drive Wa...