CF3000 InstAllAtIon And oPerAtIon MAnuAl
25-14682-A July 2019 www.eaton.com
Maintenance
Maintenance
Functions: See User Manual for full details .
Daily inspection
Check that only the green “POWER ON” indicator shows . Inspect for any fault
indication . Notify any faults to a system supervisior .
Weekly test
Check indicators .
Press Supervisor mode on the top left of the touch screen . Enter passcode . Select
“others” tab . Press the button labled weekly test, confirm you wish to perform the
test and the amber “System Test” LED will light . The panel will stay in the weekly
test mode for 5 mins before resetting . During the weekly test, trigger a smoke
Sensoror call point and check the fire panel registers the device and illuminates
the correct zonal indicator . Trigger a different device every time a weekly test is
performed ensuring devices are tested in rotation until all have been checked . It is
advisable to develop a detailed building plan highlighting devices and locations to
aid testing . The panel will reset automatically once the 5 mins have elapsed . If no
devices are triggered during the weekly test the panel will abort the test and reset
after 5 mins . Record weekly test in the table provided in this log book .
Quarterly
Check all previous log book entries and verify that remedial action has been taken .
Carry out the weekly test . Visually examine the batteries and their connections, by
loosening the screws behind printer door and opening the hinged front from the right
hand side .
Disconnect the mains supply and check that the battery is capable of supplying the
alarm sounders, by operating a call point .
Annual test
As Weekly Test and Quarterly Test above . Additionally test all sensors and call points
and check operation .
Every 2-3 years
During the normal servicing cycle check analogue levels of the detectors . If any
are approaching the pre-alarm level then the proprietary cleaning methods can be
adopted . e .g . high pressure air spray .
Every 5 years
Replace sealed lead acid battery .