38
CF3000 InstAllAtIon And oPerAtIon MAnuAl
25-14682-A July 2019 www.eaton.com
Technical specification
Auxiliary relays
The auxiliary relays provide fused volt free change over contacts. These contacts are not monitored.
Max Load
24 Volts 1 Amp
Fuse (PTC4)
1.35 Amps polyswitch
Auxiliary 24V supply
Nominal Voltage
24 Volts ±10%
Fuse (PTC5)
100 mA Polyswitch
Maximum current
30 mA
This output is not to be used for Fire protecting equipment or Fire alarm routing Equipment Any power taken from
the alarm system will effect the standby duration.
terminal blocks: do not use excessive force when tightening the screws on the
terminal block
Printer (Optional)
Type
High speed thermal
Number of characters per Line
40
Type of paper
58mm x 46mm Thermal Roll
Replacement paper roll order code
ADF6PRINTERPAPER