Compatible Equipment
Micro interfaces
A range of micro interfaces modules are also available:
MIu872
is a compact single zone input, soft addressed, microinterface, incorporating
integral short circuit isolators . It is fully compatible with the current range of Eaton
analogue fire detection panels . It is suitable for interfacing a zone of up to 20
conventional Eaton detectors onto a Eaton analogue fire panel . It will operate with
any Eaton conventional detector in configuration with a schottky diode type base .
400008FIre-0022X (MCIM)
is a compact input module used to accept input signals
from external equipment such as beam detectors, flow switches, valve monitor
switches etc . The panel can be programmed to perform different actions based on
the state of the input . The maximum number of input devices per loop is 200 .
400010FIre-0024X (MCoM)
is a compact single channel output unit for general
external equipment control . This device is identified as an I/O device by a Eaton
addressable panel . The maximum number of I/O devices per loop is 20 .
400012FIre-0026X (MCoM-s)
is a compact single channel output unit . This device
is identified as a sounder output by a Eaton addressable panel and will react to
evacuate commands . The maximum number of sounder devices per loop is 60 .
400011FIre-0025X (MCoM-r)
is a compact single channel output unit used to
control or signal external equipment which require removal of power for reset
purposes . This device is identified as an I/O device by a Eaton addressable panel .
The maximum number of I/O devices per loop is 20 .
MCoM-FC
is a compact single channel output unit used in conjunction with the
Fan Controller (FC6/FC18) for the control of smoke extraction fans . This device is
identified as a sounder output by a Eaton addressable panel but does not react to
the evacuate command . The maximum number of sounder devices per loop is 60 .