Technical specification
Alarm verification (option not required by en54 pt2)
This mode is programmed at access level 3 . This has the flexibility to delay the
activation of detectors by 30 seconds .
In the event of an alarm from a detector, the led of the detector will be illuminated
and no alarm will be displayed on the panel . The detectors are checked continuously
for 30 seconds . If after this time, the detector is still in alarm, the output will be
activated otherwise the detector will be reset .
timer t1/t2 (option not required by en54 pt2)
This mode is set on at access level 3 and is a commonly used by
Eastern European Countries .
In the event of a Fire the timer T1 can be set from 1 to 3 mins where the alarm will
be displayed on the panel and no output activation, if during this time the alarm is
acknowledged then timer T2 can be set from 1-10 mins where the alarm can be
investigated and alarm reset .
However if timer T1 & T2 time out during alarm activation, the outputs
will be activated .
timer t1/t2 with Call point override (option not required by en54 pt2)
This is similar to the above except a call point alarm will activate the output instantly .