background image

6

Installation manual 10679

Effective October 2017

BSPA Type 1 and Type 2 surge protective devices

Eaton.com/bussmannseries

6.6 Wiring  installation

IMPROPER WIRING COULD CAUSE DEATH, INJURY AND/

OR EQUIPMENT DAMAGE. ONLY LICENSED/QUALIFIED 

ELECTRICIANS WHO ARE TRAINED IN THE INSTALLATION AND 

SERVICE OF ELECTRICAL SERVICES ARE TO INSTALL AND 

SERVICE THIS EQUIPMENT.
TO MAXIMIZE THE SPD’S PERFORMANCE, TWIST AND BIND 

THE WIRES TOGETHER TO REDUCE THE IMPEDANCE OF THE 

WIRE.
ARC FLASH DURING INSTALLATION COULD CAUSE INJURY 

OR DEATH. USE APPROPRIATE SAFETY PRECAUTIONS AND 

EQUIPMENT FOR ARC FLASH PROTECTION.

Locate the electrical system’s applicable wiring schematic in Section 

7. Wiring diagrams

.

Turn 

OFF

 power to the electrical equipment being connected to the 

BSPA in accordance with NEC, CEC, state, county and local codes 

for all safety ratings.
The BSPA units covered in this manual are designed with internal 

overcurrent protection and do not require an external overcurrent 

protective device (OCPD) unless otherwise required by NEC, UL, 

and local electrical requirements to protect electrical conductors. 

NEC Article 310.15 (B) (16) defines the maximum rating of the OCPD 

required to protect the electrical conductors.
NEC shows 10 AWG conductors at 60°C typically requiring a 1-pole 

(for single-phase systems), 2-pole (for split-phase systems) or 3-pole 

(for 3-phase systems) 30 A branch circuit breaker to protect BSPA 

conductors.
Twist and bind the wires of the BSPA unit tightly together. To 

optimize BSPA performance, minimize overall lead length. To 

maximize performance for wire lengths longer than four inches, 

phase wires should be twisted once for each four inches of wire 

length.

Note

: To maximize the BSPA’s performance, 10 AWG wire length 

should be less than 14” (35cm) twisted and bound together.
If remote monitoring is required, connect the Form C relay contact 

wiring to an alarm or building monitoring system. These relay 

contacts are rated 2 A at 30 Vdc/250 Vac
Refer to Table 1 – BSPA Form C wire color codes for color codes of 

relay wires (shown in the energized state).

Note

: Utilization of Form C contacts is optional. Connecting Form C 

wires is not required for the proper BSPA operation.
Tighten and recheck all connections and mounting.

Contact

Color coding

COM

Blue/white

NO

Red/white

NC

Orange/white

Table 1. BSPA Form C wire color code.

Blue/white

Red/white

Orange/white

Common

NO (normally open)

NC (normally closed)

Form C Contact relay wire color codes

7. Wiring diagrams

Phase wire

Color code

L1 (Phase A)

Black

L2 (Phase B)

Black

L3 (Phase C)

Black

Neutral

White

Ground / protected earth

Green with yellow stripe

 Table 2. BSPA phase wire color codes.

Figure 8. Single-phase (2W+G).

Figure 9. Split-phase (3W+G).

Содержание BUSSMAN Series

Страница 1: ...MOV while supporting power frequency voltage The Type 2 BSPA models equipped with EMI filtering are designed to protect sensitive equipment from electrical noise Proper installation is critical to ensure the BSPA unit operates as intended The Type 1 BSPA units are intended for installation between the secondary of the service transformer and the lineside of the service equipment overcurrent protec...

Страница 2: ... accordance with established safety practices d is trained to render first aid e has received safety training to recognize and avoid the hazards involved f has the skills and knowledge pertaining to the construction and operation of this equipment and its installation IMPORTANT These procedures do not claim to cover all possible details or variations encountered with the installation of a Surge Pr...

Страница 3: ...identifies the unit s specifications and permits specifying any combination to meet requirements BSPA 200 208Y 8 P BSPA Product family Surge rating per phase Voltage system code Options NEMA enclosure For example BSPA unit catalog number BSPA200208Y8P where BSPA BSPA series 200 peak surge current rating 50 kA 200 kA 208Y voltage code and system configuration 8 feature option 1 8 P enclosure type N...

Страница 4: ...S POSSIBLE SEE FIGURE 3 6 2 Panel mounted The preferred mounting of the BSPA is directly to the electrical panel with its integrated male connector hub and the supplied 3 4 trade size conduit locknut Insert the wires through the panel wall being careful not to damage the wire insulation Install the provided locknut and tighten to 20 3 lb in 2 3 N m If the installation requires the NEMA 4X rating i...

Страница 5: ...ncluded 3 4 14 NPS external thread Locknut Mounting feet included 36 inch long wires 3 75 95 3 2 38 60 4 8 48 215 4 10 25 260 4 11 50 292 1 7 48 190 0 9 25 235 0 10 50 266 7 4X Ø 0 223 0 80 20 3 6 67 169 4 0 0747 THK 1 51 38 4 1 51 38 4 6 4 Enclosure mounting feet and dimensions The mounting feet attach to the bottom of the enclosure with the provided screws hardware to mount the feet to wall are ...

Страница 6: ...C typically requiring a 1 pole for single phase systems 2 pole for split phase systems or 3 pole for 3 phase systems 30 A branch circuit breaker to protect BSPA conductors Twist and bind the wires of the BSPA unit tightly together To optimize BSPA performance minimize overall lead length To maximize performance for wire lengths longer than four inches phase wires should be twisted once for each fo...

Страница 7: ... product distributor or Bussmann series product representative as the SPD may be damaged 8 3 Options audible alarm and Form C relay Note Using Form C contacts is optional Connection is not required for the proper BSPA operation The audible alarm and Form C relay are tied to the phase LEDs on the BSPA enclosure If protection to one or more phases is lost the following will occur Single split and 3 ...

Страница 8: ...utlined in appropriate Bussmann Division selling policies or other contractual agreements between the parties This manual is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and the Bussmann Division NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FI...

Страница 9: ...re to give any advice or recommendations by the Bussmann Division shall not constitute any warranty by or impose any liability upon the Bussmann Division AND IS IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESSED IMPLIED OR STATUTORY AS TO THE MERCHANTABILITY FITNESS FOR PURPOSE SOLD PRODUCTIVENESS OR ANY OTHER MATTER In no event shall the Bussmann Division be liable for special or consequential dam...

Страница 10: ...t of Eaton CSA is a registered trademark of the Canadian Standards Group NEC is a registered trademark of the National Fire Protection Association UL is a registered trademark of the Underwriters Laboratories Inc Eaton 1000 Eaton Boulevard Cleveland OH 44122 Eaton com Bussmann Division 114 Old State Road Ellisville MO 63021 United States Eaton com bussmannseries 2017 Eaton All Rights Reserved Prin...

Отзывы: