background image

7

Installation manual 10679

Effective October 2017

BSPA Type 1 and Type 2 surge protective devices

Eaton.com/bussmannseries

Figure 11. Three-phase Wye (4W+G).

8. Operation

8.1 Power up and system checkout

Switch main panel power to 

ON

 and then switch BSPA’s branch 

circuit breaker to 

ON

. One LED should light for each phase voltage 

being protected. Single-phase electrical systems will light only one 

LED, split-phase systems light two LEDs, and three-phase systems 

will light all three LEDs.
If the connected LEDs do not light, remove power, re-check 

connections, and test again. If the LEDs still do not light, contact 

your local authorized Bussmann series product distributor or 

Bussmann series product representative, as the SPD may be 

damaged.

8.2 LED color states

The LEDs located on the BSPA have three LED color states:

Green

 – fully protected

Yellow

 – loss of Neutral-to-Ground protection

Red

 – loss of phase protection

If the electrical system is single-, split- or 3-phase, the BSPA will 

have either one, two or three LEDs illuminated green, respectively. 

Each LED will illuminate when its associated phase voltage is 

present.
If any of these LEDs are yellow or red, a problem may exist with 

incoming power, wiring, branch circuit breaker wiring or within the 

BSPA itself. Disconnect power, check connections and test again. If 

the LEDs are still yellow or red, disconnect power to the BSPA and 

contact your local authorized Bussmann series product distributor 

or Bussmann series product representative, as the SPD may be 

damaged.

8.3 Options: audible alarm and Form C relay

Note

: Using Form C contacts is optional. Connection is not required 

for the proper BSPA operation.
The audible alarm and Form C relay are tied to the phase LEDs on 

the BSPA enclosure. If protection to one or more phases is lost, the 

following will occur:

• 

Single-, split- and 3-phase devices - If all voltage is lost to the 

BSPA, the green LED(s) will go out, the alarm will not sound and 

the relay will not be energized

• 

Split- and 3-phase devices - If voltage to one phase is lost to the 

BSPA, that one green LED will go out, the alarm will not sound 

and the relay will stay energized (if there is another phase voltage 

present)

• 

3-phase Wye devices - If voltage to one or two phases is lost to 

the BSPA, one or two green LEDs will go out, the alarm will not 

sound and the relay will stay energized (if there is another phase 

voltage present)

• 

3-phase Delta – BSPA needs at least 2 phases to energize the 

relay and to keep the alarm from sounding (if installed)

• 

Single-, split- and 3-phase devices - If one or more LEDs turn red, 

the alarm will sound and the relay will de-energize. To silence the 

alarm, disconnect power to the BSPA and contact your authorized 

Bussmann series product distributor or Bussmann series product 

representative, as the SPD may be damaged.

Note

: Form C relay contacts are “fail safe” and only change state 

when power is applied to the BSPA and the electrical system is 

operating normally or when loss of protection is detected and yellow 

or red LEDs are illuminated.

Figure 10. Three-phase Delta (3W+G).

Содержание BUSSMAN Series

Страница 1: ...MOV while supporting power frequency voltage The Type 2 BSPA models equipped with EMI filtering are designed to protect sensitive equipment from electrical noise Proper installation is critical to ensure the BSPA unit operates as intended The Type 1 BSPA units are intended for installation between the secondary of the service transformer and the lineside of the service equipment overcurrent protec...

Страница 2: ... accordance with established safety practices d is trained to render first aid e has received safety training to recognize and avoid the hazards involved f has the skills and knowledge pertaining to the construction and operation of this equipment and its installation IMPORTANT These procedures do not claim to cover all possible details or variations encountered with the installation of a Surge Pr...

Страница 3: ...identifies the unit s specifications and permits specifying any combination to meet requirements BSPA 200 208Y 8 P BSPA Product family Surge rating per phase Voltage system code Options NEMA enclosure For example BSPA unit catalog number BSPA200208Y8P where BSPA BSPA series 200 peak surge current rating 50 kA 200 kA 208Y voltage code and system configuration 8 feature option 1 8 P enclosure type N...

Страница 4: ...S POSSIBLE SEE FIGURE 3 6 2 Panel mounted The preferred mounting of the BSPA is directly to the electrical panel with its integrated male connector hub and the supplied 3 4 trade size conduit locknut Insert the wires through the panel wall being careful not to damage the wire insulation Install the provided locknut and tighten to 20 3 lb in 2 3 N m If the installation requires the NEMA 4X rating i...

Страница 5: ...ncluded 3 4 14 NPS external thread Locknut Mounting feet included 36 inch long wires 3 75 95 3 2 38 60 4 8 48 215 4 10 25 260 4 11 50 292 1 7 48 190 0 9 25 235 0 10 50 266 7 4X Ø 0 223 0 80 20 3 6 67 169 4 0 0747 THK 1 51 38 4 1 51 38 4 6 4 Enclosure mounting feet and dimensions The mounting feet attach to the bottom of the enclosure with the provided screws hardware to mount the feet to wall are ...

Страница 6: ...C typically requiring a 1 pole for single phase systems 2 pole for split phase systems or 3 pole for 3 phase systems 30 A branch circuit breaker to protect BSPA conductors Twist and bind the wires of the BSPA unit tightly together To optimize BSPA performance minimize overall lead length To maximize performance for wire lengths longer than four inches phase wires should be twisted once for each fo...

Страница 7: ... product distributor or Bussmann series product representative as the SPD may be damaged 8 3 Options audible alarm and Form C relay Note Using Form C contacts is optional Connection is not required for the proper BSPA operation The audible alarm and Form C relay are tied to the phase LEDs on the BSPA enclosure If protection to one or more phases is lost the following will occur Single split and 3 ...

Страница 8: ...utlined in appropriate Bussmann Division selling policies or other contractual agreements between the parties This manual is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and the Bussmann Division NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FI...

Страница 9: ...re to give any advice or recommendations by the Bussmann Division shall not constitute any warranty by or impose any liability upon the Bussmann Division AND IS IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESSED IMPLIED OR STATUTORY AS TO THE MERCHANTABILITY FITNESS FOR PURPOSE SOLD PRODUCTIVENESS OR ANY OTHER MATTER In no event shall the Bussmann Division be liable for special or consequential dam...

Страница 10: ...t of Eaton CSA is a registered trademark of the Canadian Standards Group NEC is a registered trademark of the National Fire Protection Association UL is a registered trademark of the Underwriters Laboratories Inc Eaton 1000 Eaton Boulevard Cleveland OH 44122 Eaton com Bussmann Division 114 Old State Road Ellisville MO 63021 United States Eaton com bussmannseries 2017 Eaton All Rights Reserved Prin...

Отзывы: