Eaton 9PX Lithium-Ion User Guide P-164001006—Rev 02
23
33..99
C
Coonnnneeccttiioonn w
wiitthh aa H
Hoottssw
waapp M
MB
BP
P M
Moodduullee (( O
Oppttiioonnaall A
Acccceessssoorryy))
The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected
loads.
9PX 2000RT-L
MBP-120
LOAD
15
28
1
8
2
4
3
5
6
9
10
11
7
29
33
34
35 36
9PX 3000RT-L
MBP-130
LOAD
15
28
1
8
2
4
3
5
6
9
10
11
7
29
33
34
35 36
1. Connect the input
36
on the
HotSwap MBP module to the
AC-power source.
2. Connect the UPS input cable
1
to
the “UPS Input socket”
35
on the
HotSwap MBP module.
3. Connect the UPS outlet
5
to the
“UPS Output”
34
on the HotSwap
MBP module (using the cable
28
supplied for G models).
These cables and the connectors
are marked in red.
4. Connect the equipment to the
outlets
29
on the HotSwap MBP
module. These outlets differ,
depending on the version of the
HotSwap MBP module.
Caution: when using HotSwap
MBP, do not use UPS outlets to
directly power equipment. As
operating the bypass switch
33
will cut supply voltage to the
equipment.
* 9PX 1500RT-L: To connect to MBP-115,
follow the same procedure as for the
9PX 2000RT / 9PX 3000RT.
Содержание 9PX2000RT-L
Страница 20: ...14 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 User Settings ...
Страница 36: ...30 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 UPS Remote Control Functions ...
Страница 46: ...40 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 Recycling The Used Equipment ...
Страница 50: ...44 Eaton 9PX Lithium Ion User Guide P 164001006 Rev 02 CE Compliance Contact ...
Страница 56: ...P 16400100602 P 164001006 02 ...