22
3.3.3 EBM Wiring Connection
It is possible to connect more than one EBM in order to achieve any level
of autonomy without mains power. Connect any Battery Boxes in a
cascade as shown in the figure below:
1.
CONNECTION: Use 3 cables with 10 mm
2
section (Earth, +, N and -)
2. Connect the wires to the relative terminals, following exactly the
instructions given below:
For 9E6Ki, 9E10Ki, 9E10KiXL
a - Make sure that the fuse holder of the external battery box is open.
b -
Connect the earth (PE) wire to EBM’s earth (PE) screw
c - Connect the positive (+) branch wire to EBM
’s positive (+) terminal
.
d - Connect the negative (-) branch wire to EBM
’s negative (-) terminal.
The suggested tighten force is 1.6Nm. (Detailed wiring diagram see fig
3-9~10)
Fig.3-8 EBM terminal view (Fuse for 9E6Ki,
9E10Ki, 9E10KiXLwithout Neutral)