Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04
19
Weight and Center of Gravity (letters A, B, and C map to
Models
Dimensions
A
mm (in)
B
mm (in)
C
mm (in)
Installed
Weight
kg (lb)
432V
IBC-LW
with 75Ah Batteries (E28)
1019 (40.1)
509 (20.0)
454 (17.9)
1385 (3054)
with 100Ah Batteries (E39)
1031 (40.6)
507 (20.0)
455 (17.9)
1687 (3720)
with 135Ah Batteries (E54)
1038 (40.9)
506 (19.9)
456 (18.0)
1989 (4386)
with 103Ah Batteries (B37)
1029 (40.5)
508 (20.0)
455 (17.9)
1717 (3785)
with 95Ah Batteries (H41)
1027 (40.4)
508 (20.0)
455 (17.9)
1674 (3691)
with 125Ah Batteries (N54)
1036 (40.8)
506 (19.9)
456 (18.0)
2010 (4431)
IBC-LHW
with 103Ah Batteries (B37)
1029 (40.5)
508 (20.0)
455 (17.9)
1750 (3857)
with 95Ah Batteries (H41)
1027 (40.4)
508 (20.0)
455 (17.9)
1707 (3763)
with 125Ah Batteries (N54)
1036 (40.8)
506 (19.9)
456 (18.0)
2043 (4505)
with 135Ah Batteries (E54)
1036 (40.8)
506 (19.9)
456 (18.0)
2022 (4458)
480V
IBC-LW
with 75Ah Batteries (E28)
969 (38.1)
508 (20.0)
434 (17.1)
1500 (3308)
with 100Ah Batteries (E39)
977 (38.5)
507 (20.0)
434 (17.1)
1836 (4048)
with 135Ah Batteries (E54)
982 (38.7)
505 (19.9)
434 (17.1)
2179 (4803)
with 103Ah Batteries (B37)
975 (38.4)
507 (20.0)
434 (17.1)
1876 (4136)
with 95Ah Batteries (H41)
957 (38.4)
507 (20.0)
434 (17.1)
1829 (4032)
with 125Ah Batteries (N54)
981 (38.6)
506 (19.9)
434 (17.1)
2202 (4855)
IBC-LHW
with 103Ah Batteries (B37)
975 (38.4)
507 (20.0)
434 (17.1)
1902 (4193)
with 95Ah Batteries (H41)
975 (38.4)
507 (20.0)
434 (17.1)
1855 (4089)
with 125Ah Batteries (N54)
981 (38.6)
506 (19.9)
434 (17.1)
2228 (4913)
with 135Ah Batteries (E54)
980 (38.6)
506 (19.9)
434 (17.1)
2205 (4861)
33..22..22
IIB
BC
C P
Poow
weerr W
Wiirriinngg P
Prreeppaarraattiioonn
Read and understand the following notes while planning and performing the installation:
WARNING
As a result of the connected loads high leakage current is possible. Connection to earth ground is required for
safety and proper product operation. Do not check IBC operation by any action that includes removal of the
earth (ground) connection with loads attached.
•
Refer to national and local electrical codes for acceptable external wiring practices.
•
Material and labor for external wiring requirements are to be provided by the customer.
•
For external wiring, use 75°C copper wire.