12
Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04
NOTE
Emergency lighting and power equipment battery cabinets (UL924) are rated for
operation in a 20°–30°C (68°–86°F) temperature environment.
•
The batteries are rated for a 25°C (77°F) ambient temperature to extend their useful life.
•
Maximum Relative Humidity: 5–95%, noncondensing
CAUTION
It is recommended for optimal battery life and discharge performance to keep the ambient air temperature the
battery is used in at 25°C (77°F). Operating temperatures above the recommended range will result in
decreased battery life and performance, and will reduce or void the battery warranty. Refer to Eaton's Terms
and Conditions of Sale with Battery Replacement Coverage and the Battery Replacement Price Book for more
information. These documents can be found at
www.eaton.com/powerquality
or contact your service
representative for information on how to obtain copies.
The IBC operating environment must meet the weight requirements shown in
,
or
and the size requirements shown in
through
. Dimensions are in millimeters (inches).
Specifications are subject to change.
Table 1. Eaton 93PM IBC-LW (432V) Cabinet Weights
Model
Weight kg (lb)
Shipping
Installed
Point Loading
Eaton 93PM Universal Integrated Battery
Cabinet-Large with E28 Batteries
1430 (3154)
1385 (3054)
6 at 231 (509)
Eaton 93PM Universal Integrated Battery
Cabinet-Large with E39 Batteries
1732 (3820)
1687 (3720)
6 at 281 (620)
Eaton 93PM Universal Integrated Battery
Cabinet-Large with E54 Batteries
2034 (4486)
1989 (4386)
6 at 332 (731)
Eaton 93PM Universal Integrated Battery
Cabinet-Large with B37 Batteries
1762 (3885)
1717 (3785)
6 at 286 (631)
Eaton 93PM Universal Integrated Battery
Cabinet-Large with H41Batteries
1719 (3791)
1674 (3691)
6 at 279 (615)
Eaton 93PM Universal Integrated Battery
Cabinet-Large with N54 Batteries
2055 (4531)
2010 (4431)
6 at 335 (739)
Содержание 93PM IBC-LHW
Страница 4: ......
Страница 78: ...P 16400054104 P 164000541 04...