Bypass and output overcurrent protection and bypass and output disconnect switches must be provided
by the user.
4
4..5
5
U
Unnp
paacckk aanndd uunnllooaadd tthhee U
UPPSS
Before you start to unpack and unload the UPS, check the TipNTell indicator on the package surface and
the DropNTell indicator on the UPS after unpacking (see step 2 below). If the equipment has been
correctly transported in the upright position, the indicator should be intact. If the indicator arrow has turned
all blue, contact the appropriate parties to report inappropriate transportation.
WARNING
The UPS cabinet is heavy. If the unpacking instructions are not closely followed,
the cabinet may tip over and cause serious injury.
Do not tilt the UPS cabinet more than 10 degrees from the vertical or the cabinet
may tip over.
For transportation purposes, the UPS cabinet is bolted onto a wooden pallet. To remove the pallet, follow
this procedure.
1. Before you unload the cabinet from the pallet, use a forklift or other material handling equipment to
move the cabinet to the installation area. Insert the forks of the forklift between the runs on the bottom
of the pallet.
2. Make a visual inspection and make sure that there are no signs of shipping damages. Examine the
indicators. See the DropNTell inside the package.