UPS INSTALLATION PLAN AND UNPACKING
EATON
Powerware
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
S
164201764 Rev 1
www.powerware.com
3−13
Table 3-8. UPS Intercabinet Power Cable Terminations for the Four UPM Powerware 9395−1100/1000 and 9395−1100/1100, and the Three UPM
Powerware 9395−1100/650, 9395−1100/750, and 9395−1100/825
Terminal Function
Terminal
Function
Bus Landing
Tightening Torque
Nm (lb ft)
Stud
AC Input to UPM Section
E1A (UPM 1)
E1A (UPM 2)
E1A (UPM 3)
E1A (UPM 4 – Four UPM Model)
Phase A
3 – stud mounting
12 (8.3)
M8
E2A (UPM 1)
E2A (UPM 2)
E2A (UPM 3)
E2A (UPM 4 – Four UPM Model)
Phase B
3 – stud mounting
12 (8.3)
M8
E3A (UPM 1)
E3A (UPM 2)
E3A (UPM 3)
E3A (UPM 4 – Four UPM Model)
Phase C
3 – stud mounting
12 (8.3)
M8
AC Output from UPM Section
E9A (UPM 1)
E9A (UPM 2)
E9A (UPM 3)
Phase A
3 – stud mounting
12 (8.3)
M8
E10A (UPM 1)
E10A (UPM 2)
E10A (UPM 3)
Phase B
3 – stud mounting
12 (8.3)
M8
E11A (UPM 1)
E11A (UPM 2)
E11A (UPM 3)
Phase C
3 – stud mounting
12 (8.3)
M8
E12A (UPM 1)
E12A (UPM 2)
E12A (UPM 3)
Neutral
3 – stud mounting
12 (8.3)
M8
DC Input to UPM Section
1E4A (UPM 1)
2E4A (UPM 2)
3E4A (UPM 3)
Positive
6 – stud mounting
(2 per UPM)
12 (8.3)
M8
1E5A (UPM 1)
2E5A (UPM 2)
3E5A (UPM 3)
Negative
6 – stud mounting
(2 per UPM)
12 (8.3)
M8
Table 3-9. Supplied Intercabinet Wiring Terminal Hardware Kit
Part
Size
Quantity
Terminals Used On
Eaton Part Number
Flat Washer
M8
36
UPM AC Input, UPM Battery Input, UPM AC
Output, and Neutral
180500036−080
Conical Washer
M8
36
UPM AC Input, UPM Battery Input, UPM AC
Output, and Neutral
180500037−080
Nut
M8
36
UPM AC Input, UPM Battery Input, UPM AC
Output, and Neutral
180200001−05