UPS INSTALLATION PLAN AND UNPACKING
EATON
Powerware
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
S
164201764 Rev 1
www.powerware.com
3−2
For Field Installed UPM (FI−UPM) weights and dimensions, refe to the
Powerware
9395 Field Installed UPM Mechanical Installation Manual
, listed in paragraph 1.8 on
page 1−7.
Table 3-1. UPS Cabinet Weights
Model
Section
Weight
kg (lb)
Shipping
Installed
Powerware 9395−1100/1000
ISBM
1850 (4078)
1750 (3858)
UPM
1590 (3505)
1482 (3267)
Powerware 9395−1100/1100
ISBM
1850 (4078)
1750 (3858)
UPM
1590 (3505)
1482 (3267)
The UPS cabinet uses forced air cooling to regulate internal component temperature.
Air inlets are in the front of the cabinet and outlets are in the top. Allow clearance in
front of and above each cabinet for proper air circulation. The clearances required
around the UPS cabinet are shown in Table 3-2.
Table 3-2. UPS Cabinet Clearances
From Top of Cabinet
457.2 mm (18
"
) minimum clearance for ventilation
From Front of Cabinet
914.4 mm (36
"
) working space
From Back of Cabinet
None Required
From Right Side of Cabinet
152.4 mm (6
"
) working space
From Left Side of Cabinet
None Required
The basic environmental requirements for operation of the UPS are:
S
Ambient Temperature Range:
0–40°C (32–104°F)
S
Recommended Operating Range: 20–25°C (68–77°F)
S
Maximum Relative Humidity:
95%, noncondensing
C
A
U
T
I
O
N
If battery systems are located in the same room as the UPS, the battery manufacturer’s environmental
requirements should be followed if they are more stringent than the UPS requirements. Operating
temperatures above the recommended range will result in decreased battery life and performance, and may
reduce or void the battery warranty.
The UPS ventilation requirements are shown in Table 3-3.
Table 3-3. Air Conditioning or Ventilation Requirements During Full Load Operation
Model
Rating
Input/Output
Voltage
Heat Rejection
BTU/hr
1000 (kg−cal/hr)
Ventilation Required for Cooling Air Exhaust
Powerware 9395−1100/1000
1000 kVA
480/480
195 (49127)
Approximately 3020 liter/sec (6400 cfm)
Powerware 9395−1100/1100
1100 kVA
480/480
215 (54040)
Powerware 9395−1100/650
650 kVA
480/480
127 (31933)
Approximately 2265 liter/sec (4800 cfm)
Powerware 9395−1100/750
750 kVA
480/480
146 (36845)
Powerware 9395−1100/825
825 kVA
480/480
161 (40530)