9000X AF Drives User Manual
5-6
For more information visit:
www.eaton.com
MN04001004E
June 2009
Keypad Control Menu (M2)
In the Keypad Control Menu, you can set the frequency reference, choose the motor
direction for keypad operation, and determine if the STOP button will be active at all
times. See Figure 5-4.
Figure 5-4: Keypad Control Menu
This parameter number varies for different applications.
R2.1
Keypad
Reference
Range: Min. Frequency — Max. Frequency
Units: Hertz
Keypad Reference
This displays and allows the operator to edit the keypad frequency reference. A
change takes place immediately. This reference value will not influence the output
frequency unless the keypad has been selected as the active control place.
P2.2
Keypad
Direction
Range: Forward, Reverse
Default: Forward
Keypad Direction
This allows the operator to change the rotation direction of the motor. This setting
will not influence the rotation direction of the motor unless the keypad has been
selected as the active control place.
P2.3
Stop Button
Active
Range: Yes, No
Default: Yes
StopButtonActive
By default, pushing the STOP button will always stop the motor regardless of the
selected control place. If this parameter is set to No, the STOP button will stop the
motor only when the keypad has been selected as the active control place.
M2 Keypad Control
R2.1 Keypad Reference
P2.2 Keypad Direction
. . .
P2.x Stop Button Active