9000X AF Drives User Manual
MN04001004E
For more information visit:
www.eaton.com
C-29
June 2009
F51 — External Fault
Figure C-32: F51 — External Fault
Actual status =
Monitored status ?
Yes
No
Read status of programming input from
corresponding monitoring page
Check I/O option board, replace if necessary
External reason for activating the fault
Set parameters to match with application
Test and/or replace control board
with functioning one according to
instructions in service manual.
Replace defective parts as
recommended in spare parts lists.
Make corrections to the external devices
F51
Clear fault memory