Seismic Data Requirements for Eaton UPS Equipment Installation User’s Guide 164000050—Rev 05
15
Table 7. 9395/P/XC Unit and Fastener Requirements from Unit to Floor (Continued)
Product
Type
Bolt Type and Size
Torque
Quantity
9395P
continued
900 kVA UPS (3X-UPM)
Class 8.8, M12
83 Nm
61 lb-ft.
14
1200 kVA UPS (3X-UPM)
20
1200 kVA UPS (4X-UPM)
22
9395XC
1500 kW (HD) UPS
Class 8.8, M12
66 Nm
64 lb-ft.
16
1500 kW (LD) UPS
16
NOTE
The torque value for each bracket-to-cabinet connecting bolt is Class 8.8
M12
Bolt = 83 Nm [61 lb-ft.]
Eaton 9395, 9395P and 9395XC Foundation Plan and Mounting Requirements
Содержание 9 55 Series
Страница 62: ...16400005005 164000050 05...