Seismic Data Requirements for Eaton UPS Equipment Installation User’s Guide 164000050—Rev 05
7
Table 5. 9390 Unit Seismic Displacement Requirements (Continued)
Type
Front to Back
Side to Side
100-160 UPS kVA
48 mm
48 mm
UPS 100-160 kVA w/sidecar
48 mm
48 mm
20-80 kVA IDC
140 mm
140 mm
100-160 kVA IDC
108 mm
108 mm
IAC-B and IAC-T
36 mm
36 mm
IAC-D
36 mm
36 mm
Consideration must be given to attachments (conduits, bus duct, etc.) made to the top of the equipment.
Attachments must have provisions to accommodate the displacement of the equipment indicated in
Entry from the bottom of the equipment eliminates the need for accommodating this motion for attachments.
33..22
C
Ceenntteerr ooff G
Grraavviittyy
For seismic calculations, the center of gravity can be approximated using the dimensions in
with
respect to the left side bracket's front mounting hole (x,y,z origin).
Table 6. 9390 Unit Center of Gravity Specifications
Type
X (left to right)
Y (front to rear)
Z (bottom to top)
20-80 kVA UPS
252 mm
248 mm
940 mm
20-80 kVA UPS w/sidecar
393 mm
248 mm
940 mm
100-160 UPS kVA
482 mm
248 mm
965 mm
UPS 100-160 kVA w/sidecar
540 mm
248 mm
965 mm
20-80 kVA IDC
482 mm
248 mm
965 mm
100-160 kVA IDC
575 mm
248 mm
965 mm
IAC-B and IAC-T
319 mm
248 mm
965 mm
IAC-D
319 mm
248 mm
965 mm
33..33
P
Poow
weerr C
Caabblleess
It is recommended that power cables be lashed together at least every meter within the equipment. Refer to
the appropriate Eaton UPS instruction and operation manual for other requirements related to securing power
cables.
33..44
99339900 FFlloooorr P
Pllaann S
Seeccuurriinngg D
Diim
meennssiioonnss
through
detail the measurements for attaching the 9390 seismic brackets to the floor of the
building. The drawings are for reference only and are not to scale. Dimension are in millimeters (inches).