Instruction Book
Effective: November 2017
Page 57
IB131016EN
For more information visit:
www.Eaton.com
Table 6.4 Troubleshooting Guide (continued from previous page)
Symptom
Probable Cause
Corrective Actions
Circuit breaker cannot be closed remotely
(can be closed locally)
Spring release (closing) coil supply
voltage low or spring release faulty
Check power supply voltage;
replace spring release if faulty
Secondary contact wiring problem
Make sure electrical pin and socket
connectors are properly seated in
molded plug. Verify proper wiring
Latch check switch open
Bad switch or not reset
Circuit breaker cannot be closed locally
(but can be closed remotely)
Opening and/or closing
pushbuttons locked
Check reason for lock
Circuit breaker does not recharge
electrically but will recharge manually
Charging motor supply voltage
absent or too low (< minimum of
range )
Check charging motor electrical
circuit voltage (check under load)
Charging motor faulty
Replace charging motor assembly
Содержание 50 VCP-TR16
Страница 2: ......
Страница 19: ...Instruction Book Effective November 2017 Page 13 IB131016EN For more information visit www Eaton com...
Страница 69: ...Instruction Book Effective November 2017 Page 63 IB131016EN For more information visit www Eaton com...
Страница 71: ...Instruction Book Effective November 2017 Page 65 IB131016EN For more information visit www Eaton com...
Страница 76: ...Instruction Book Page 70 Effective November 2017 For more information visit www Eaton com IB131016EN...