Network Management Card
– User Manual
34003991EN/EB
Page
95/118
7.4.3 Data for Pulsar MX 4000 / 5000 / 10000 and EX 5 / 7 / 11 RT
7.4.3.1 Status table
Status description
Status to 0
Status to 1
Word (hex)
Bit
Load protected
no
yes
40
0
UPS coupled
no
yes
40
1
Unit general alarm
no
yes
40
2
UPS in backup
no
yes
40
4
Battery low warning
no
yes
40
5
Low battery
no
yes
40
6
Operation on static switch
no
yes
40
7
Communication fault
absent
present
40
9
UPS overload
no
yes
40
A
Emergency stop
absent
present
40
B
Battery to be checked
no
yes
40
D
Device ventilation fault
no
yes
40
E
Manual bypass switch (Q3BP)
open
closed
41
6
UPS in “eco” mode
no
yes
41
7
Battery present
absent
present
42
0
Mains 1 voltage out of tolerance
no
yes
44
8
Mains 1 fuse fault
no
yes
44
9
Mains 1 frequency out of tolerance
no
yes
44
B
Redundancy lost
no
yes
45
7
Maintenance position
no
yes
46
1
Mains 2 overload
no
yes
46
5
Mains 2 thermal overload
no
yes
46
6
Output on bypass
no
yes
46
7
Mains 2 frequency out of tolerance
no
yes
46
9
Mains 2 voltage out of tolerance
no
yes
46
A
Phase M2 out of tolerance
no
yes
46
B
Mains 2 internal fault
absent
present
47
2
Charger general fault
no
yes
49
0
Battery charge
no
yes
49
1 & 3
Converter fault
no
yes
4A
1
Inverter major fault
no
yes
4C
1
Inverter overload
no
yes
4C
2
Inverter thermal overload
no
yes
4C
3
Inverter limitation
no
yes
4C
4
UPS fuse fault
absent
present
4C
5