7.4.4.3 Measurements table
Description of the physical quantity
Word (hex)
Unit
I1 (I phase 1) mains 1
100
A
I2 (I phase 2) mains 1
101
A
I3 (I phase 3) mains 1
102
A
I1 (I phase 1) mains 2
106
A
I2 (I phase 2) mains 2
107
A
I3 (I phase 3) mains 2
108
A
I1 (I phase 1) output
109
A
I2 (I phase 2) output
10A
A
I3 (I phase 3) output
10B
A
I battery
10E
A
U12 mains 1
115
V
U23 mains 1
116
V
U31 mains 1
117
V
U mains 2 (phase 1)
11E
V
U mains 2 (phase 2)
11F
V
U mains 2 (phase 3)
120
V
U12 mains 2
121
V
U23 mains 2
122
V
U31 mains 2
123
V
U1N output
124
V
U2N output
125
V
U3N output
126
V
U12 output
127
V
U23 output
128
V
U31 output
129
V
U battery
12D
V
Output active power (phase 1)
130
W
Output active power (phase 2)
131
W
Output active power (phase 3)
132
W
Output apparent power (phase 1)
133
VA
Output apparent power (phase 2)
134
VA
Output apparent power (phase 3)
135
VA
Output total active power
136
W
Output total apparent power
137
VA
% output load level
139
%
Peak factor phase 1 x 100
13A
-
Peak factor phase 2 x 100
13B
-
Peak factor phase 3 x 100
13C
-
Power factor x 100
13D
-
Mains 1 frequency
13E
dHz
Mains 2 frequency
140
dHz
Output frequency
141
dHz
Battery backup time
149
Min
Battery charging level
14B
%