Network Management Card
– User Manual
34003991EN/EB
Page
115/118
8.2.2 Table des TRAPS : (1.3.6.1.4.1.705.1.11)
SNMP traps are sent when alarms appears and desappears.
Level : 1:informational , 2:major, 3:critical
MIB TRAP
Trap #
Level
-upsmgBatteryFault
Trap 1
Level 3
-upsmgBatteryOK
Trap 2
Level 1
-upsmgAtLowBattery
Trap 5
Level 3
-upsmgFromLowBattery
Trap 6
Level 1
-upsmgChargerFault
Trap 7
Level 3
-upsmgChargerOK
Trap 8
Level 1
-upsmgOnBattery
Trap 11
Level 2
-upsmgReturnFromBattery
Trap 12
Level 1
-upsmgOnByPass
Trap 13
Level 2
-upsmgReturnFromByPass
Trap 14
Level 1
-upsmgUtilityFailure
Trap 17
Level 2
-upsmgUtilityRestored
Trap 18
Level 1
-upsmgOverLoad
Trap 21
Level 3
-upsmgLoadOK
Trap 22
Level 1
-upsmgOverTemperature
Trap 23
Level 3
-upsmgTemperatureOK
Trap 24
Level 1
-upsmgOffToStart
Trap 29
Level 2
-upsmgOffInProgress
Trap 31
Level 3
-upsmgCommunicationFailure
Trap 37
Level 3
-upsmgCommunicationRestored
Trap 38
Level 1
-upsmgRedundancyLost
Trap 65
Level 2
-upsmgRedundancyOK
Trap 66
Level 2
-upsmgProtectionLost
Trap 67
Level 2
-upsmgProtectionOK
Trap 68
Level 2
If the Environment Sensor is detected , the following information are managed.:
- upsEnvironmentComFailure
Trap 53
Level 2
- upsEnvironmentComOK
Trap 54
Level 2
- upsEnvironmentTemperatureLow
Trap 55
Level 2
- upsEnvironmentTemperatureHigh
Trap 56
Level 2
- upsEnvironmentTemperatureOK
Trap 57
Level 2
- upsEnvironmentHumidityLow
Trap 58
Level 2
- upsEnvironmentHumidityHigh
Trap 59
Level 2
- upsEnvironmentHumidityOK
Trap 60
Level 2
- upsEnvironmentInput1Closed
Trap 61
Level 2