background image

www.eaton.com

 

 

 

 

Network 

Management Card  

 

 

User manual 

 

 

 

Network Management Card

 – User Manual 

34003991EN/EB

 

Page 

1/118 

 

 

 

 

 

Содержание 34003991EN/EB

Страница 1: ...www eaton com Network Management Card User manual Network Management Card User Manual 34003991EN EB Page 1 118 ...

Страница 2: ...y 10 1 3 3 Configuration 10 1 3 4 Administration 11 1 3 5 Network 11 1 3 6 Environment sensor 11 1 3 7 MIB Management Information Base 12 1 3 8 Default parameters 13 2 INSTALLATION 14 2 1 UNPACKING AND CHECK ON CONTENTS 14 2 2 INDICATIONS 14 2 3 INSTALLATION IN THE UPS 15 2 4 SENSOR INSTALLATION OPTION 16 3 CONFIGURATION 17 3 1 CONFIGURE IP PARAMETERS 17 3 1 1 Your network is equipped with a DHCP ...

Страница 3: ...ted by the Shutdown Timer Shutdown after 69 5 2 2 Extended power outage shutdown initiated by the Low battery power message 69 5 2 3 Case of power restoration before the end of the shutdown duration counter 70 5 3 SHUTDOWN MANAGEMENT WITH 2 NMC BOARDS 71 5 3 1 Shutdown Duration 71 5 3 2 Settings 71 6 CONFIGURATION VIA RS232 72 6 1 CHOICE 1 RESTART RESET 73 6 2 CHOICE 2 NETWORK CONFIGURATION 73 6 2...

Страница 4: ...Pulsar MX 4000 5000 10000 and EX 5 7 11 RT 95 7 4 4 Data for Pulsar MX frame 15 20 97 7 4 5 Sensor data 102 7 4 6 Other data 105 8 APPENDICES 106 8 1 TABLES OF ALARMS AND EVENTS 106 8 1 1 Table of alarms 106 8 1 2 Table of UPS events 109 8 1 3 Table of system alarms 111 8 2 SNMP OBJECTS 112 8 2 1 MGE MIB 112 8 2 2 Table des TRAPS 1 3 6 1 4 1 705 1 11 115 9 GLOSSARY 117 ...

Страница 5: ...puter network Carries out automatic shutdown of computer systems Monitors and controls all the UPSs connected to the network EATON Network Solution provides 3 main functions Supervision of the UPSs over the Network Web browser Enterprise Power Manager or SNMP NMS Protection of the computers multi platform with Network Shutdown Module for MGE Office Protection Systems UPS Netwatch for Powerware UPS...

Страница 6: ... Modules Netwatch Web Browser Network Management Systems Enterprise Power Manager sends notifications on certain events Operation may be in standard secure mode the default mode or in SSL secure mode Secure Socket Layer SSL 1 1 2 Protection of the computers servers This function is performed by Network Shutdown Module for MGE Office Protection Systems UPS Netwatch for Powerware UPS installed on ea...

Страница 7: ...egration of EATON UPSs you can use one of the Network Management System Kits for MGE devices These kits are available on the Management Pac 2 CD ROM ref 66923 The supervisor Enterprise Power Manager 1 1 4 Connection Before installing the Network Solution the UPS must be set up as indicated in the steps below Shut down the computers to be protected by the UPS Connect the UPS to a wall outlet For UP...

Страница 8: ...ad mgeops com Netwatch for Powerware UPS The software components for each platform and the user manuals are available at powerware com 1 2 Presentation of the Network Management Card NMC 1 2 1 Compatibility with UPSs The Minislot Network Management Card is compatible with the UPS listed into the compatibility list available at download mgeops com for the MGE Office Protection Systems UPS available...

Страница 9: ... to be used depends on the service provider For example sms 0660256585 votre login activmail net text messages 1 2 4 Compatibility with the Network Management Systems NMS Trap sending The Network Management Cards are compatible with the major Network Management Systems IBM Tivoli CA Unicenter HP Insight Manager The Management Pac 2 offering includes the necessary SNMP plug ins to allow an easy int...

Страница 10: ...patible 1 3 2 EMC Compatibility When correctly installed and used in accordance with the manufacturer s instructions the Network Management Card complies with the following standards Safety for ATI IEC EN 60950 1 2002 EMC EN 61000 6 2 2002 EN 61000 6 3 2002 IEC EN 62040 2 2002 As per European directives Low voltage 73 23 EEC and 93 68 EEC EMC 89 336 EEC and 93 68 EEC 1 3 3 Configuration The user c...

Страница 11: ... of logs in the non volatile memory Languages available English French Spanish German Italian On line help in English available for each page Card firmware updated via the network Card Mass settings via the network with the NMC tool 1 3 5 Network Fast ETHERNET 10 100 Mbits compatibility with auto negotiation on the RJ45 outlet 1 3 5 1 List of ports used BootP DHCP UDP 68 67 HTML TCP 80 SSL TCP 443...

Страница 12: ...allation in the event of a threshold being exceeded or on opening closure of a dry contact Connection to the card with straight CAT5 RJ45 network cables maximum card sensor distance 20 m Hot installation 1 3 7 MIB Management Information Base Compatible with MIB MGE Office Protection Systems V1 7 The list of objects managed can be found in the appendix ...

Страница 13: ...rval sec 60 10 to 99999 sec Environment log interval sec 300 10 to 99999 sec Default Language English English French Spanish German Italian Manager table empty 50 maximum Access control User name admin 10 characters maximum Password admin 10 characters maximum Community name read public 49 characters maximum Trap port 161 Non configurable Date and time Date and time adjustment Accept automatic upd...

Страница 14: ...4003991EN EB Page 14 118 2 Installation 2 1 Unpacking and check on contents The installation kit contents A Network Management Card 66102 A serial communication cable for configuration 34003918 Installation manual 34003905 2 2 Indications ...

Страница 15: ...eration Communication with the UPS is operational RS232 Orange Off Configuration menu is active On Normal operation Configuration menu is deactived Flashing Communication with the Environment Sensor option 2 3 Installation in the UPS The Network Management Card 66102 can be hot installed in all UPSs of the MGE Office Protection Systems or Powerware range equipped with a Minislot without having to ...

Страница 16: ...ing of the UPS s environment through regular measurements temperature humidity status of two external contacts It also enables notification of alarms e mail trap SNMP according to pre programmed thresholds It is connected to the Service port Settings Sensor directly on the Network Management Card with a standard Ethernet cable 20 meters maximum Recognition is automatic Supervision and configuratio...

Страница 17: ...order to access the configuration menu Connect the other end of the cable to the COM port IOIOI of a PC Launch a HyperTerminal type emulator with the following configuration Speed 9600 Data bits 8 Parity none Stop bits 1 Flow control none Locally reproduce the characters entered option deactivated Enter admin The main menu is displayed EATON NETWORK MANAGEMENT CARD 1 Reset 2 Network configuration ...

Страница 18: ...k settings 2 Modify Network settings 3 Set Ethernet speed 0 Exit Then type 1 The menu is displayed Network configuration MAC address 00 20 85 FD 1C 07 Mode Static IP IP address 166 99 21 94 Subnet mask 255 255 248 0 Gateway 166 99 17 1 Note the IP address To exit enter 0 then 0 The card is operational Note As long as the card is not connected to the network it continuously attempts to make connect...

Страница 19: ...et obtain IP settings from the network N N Static IP address 166 99 21 94 166 99 21 21 Static IP address is 166 99 21 21 Subnet Mask IP address 255 255 248 0 255 255 255 0 Subnet Mask IP address is 255 255 255 0 Gateway address IP address 166 99 17 1 166 99 17 1 Gateway address IP address is 166 99 17 1 Wait during your new configuration is saved Reset the card to take into account the new configu...

Страница 20: ...tialised previously in the Installation chapter e g http 166 99 16 16 The UPS properties home page is displayed 4 1 Optimising the performance of your browser To view status changes on the UPS in real time the browser must be configured so that it automatically refreshes all the objects on the current page Example on IE 6 Tools Internet Options General Parameters menu tick Every time this page is ...

Страница 21: ... below The different choices are the following ones UPS Status chosen by default this page gives instant access to the essential information about your UPS UPS Alarms to view the list of current alarms UPS Modules available on modular UPS to view general information on each modules About your UPS provides information on the UPS and the card in particular the model range and software version These ...

Страница 22: ...on The various icons showing the status of the UPS are Normal operation Alarm present This icon links directly to the alarm page Loss of communication with the UPS Animated synoptic An animated synoptic gives a global overview of the UPS current operating mode This synoptic is available on all On Line UPS The synoptic drawing depends on the UPS topology The different drawings are described in the ...

Страница 23: ...cation with the UPS all the elements of the synoptic are grey The various elements of the synoptic are the following ones AC Normal Input In tolerances Out of tolerances AC Normal Flow AC to DC converter powered by AC Normal AC to DC converter not powered by AC Normal AC to DC Converter Powered Not powered Internal failure ...

Страница 24: ...y test result Battery Output Flow DC to AC converter powered by battery DC to AC converter not powered by battery DC to AC Converter Input flow Energy flow present No energy flow DC to AC Converter Powered Not powered Internal failure DC to AC Converter Output Energy flow present No energy flow AC Bypass Input In tolerances Out of tolerances ...

Страница 25: ...w Energy flow present No energy flow AC Automatic Bypass Status Powered Not powered Internal failure AC Manual Bypass Flow Energy flow present No energy flow AC Manual Bypass Status Open Closed AC Output Flow Energy flow present No energy flow AC Output Load protected Load not protected ...

Страница 26: ...ents Boxes showing measurements appear when synoptic elements are hovered by the pointer See example below These measurements are available for AC to DC converter Battery DC to AC converter and automatic bypass The measurements available in these boxes depend on the UPS range ...

Страница 27: ...in output is protected Group1 and Group2 indicates if the controlled outlets if available are powered The various icons showing the status of the UPS outputs are green outlet Outlet powered red outlet Outlet not powered or not protected Battery Information Battery load level remaining battery charge in percent The information is completed with the two following labels Charging if the utility power...

Страница 28: ...ddition of these 2 values is the total number of available UPS The Minimum redundant UPS modules to trigger alarm can be configured from this page The button Save makes the card setting the parameter into the UPS A warning message informs the user about the consequences of this parameters modification The redundancy lost can generate Email notification if set in the email notification page and SNM...

Страница 29: ... active when the module has at least one alarm level Critical active when the module has a communication fault When the module is working properly with no alarms the icon is not reactive otherwise it is reactive and clicking on it makes the page Alarm Table appear Output load level Value of the percentage of load at module output Battery load level Percentage of charge available in the battery mod...

Страница 30: ... 30 118 4 2 1 4 Viewing the alarms Click on Alarm Table scroll list to view the list of current alarms The table of managed alarms is included in the appendix The level of the alarms appears like below Critical Warning Unknown Alarm table for standard UPS ...

Страница 31: ...Network Management Card User Manual 34003991EN EB Page 31 118 Alarm table for modular UPS ...

Страница 32: ...Network Management Card User Manual 34003991EN EB Page 32 118 4 2 1 5 Viewing the About your UPS window Click on About your UPS scroll list to view the information about the UPS and the card ...

Страница 33: ...e help On line contextual help in English is available at the top of each page by clicking on the Help link which is always located on the top right corner The navigation menu of the on line help is identical to that of the card s pages The Help page always opens a new window ...

Страница 34: ...ers max After the login and password are entered they remain active for 5 minutes If the browser is closed they will have to be re entered An error in either field results in systematic rejection of the requested action save page access card reboot After three unsuccessful attempts the browser must be rebooted These two fields do not travel decoded on the IT network They are encrypted with an MD5 ...

Страница 35: ...controlled outlets Shutdown of the main outlet causes the controlled outlets to shut down Controlled outlets can only be started if the master outlet is on The Check column proposes six different commands and a command is only actually started after clicking on Execute Safe power down A sequence to switch off output power is launched immediately The systems supplied are shut down correctly while t...

Страница 36: ...er down reboot This is the same switch off then on sequence as for the Safe power down reboot command but postponed by the number of seconds programmed in the Off Delay parameter Delayed On This is the same switch on sequence as for the Immediate On command but postponed by the number of seconds programmed in the On Delay parameter The Save button saves the Off Delay Toggle duration and On Delay p...

Страница 37: ...r program a reboot of the protected equipment at a set time In a shutdown sequence the Network Shutdown Modules connected to the card are informed and ensure that each machine is shut down correctly before the UPS output is switched off Up to 7 UPS shutdown sequences can be programmed in one week with a minimum shutdown delay of 30 minutes The On Off sequences are valid only if the card s time has...

Страница 38: ...n the menu to see the list of parameters When you tick the Show advanced parameters option extra parameters are displayed These parameters enable in particular adjustment of certain thresholds related to the percentage of remaining battery charge level The Output column enables each outlet to be named maximum 20 characters Note As priority is given to the main outlet the card cannot supply the con...

Страница 39: ...Important Certain UPSs do not support this option For the controlled outlets group 1 or group 2 by default The page enables programming of operation time and level in backup mode to manage outlet load shedding in the event of electric power failure Switch Off after from 0 to 99999 65535 by default defines the time during which the outlet is supplied starting from the moment of utility failure Caut...

Страница 40: ...quency of your UPS AC Output Power kVA Value of the output power of your UPS AC Output Load level Value of the percentage of load at UPS output Battery Capacity Percentage of charge available in the battery Battery Remaining time mn Estimation of the remaining backup time The save frequency of these values is defined in the System page 60 seconds by default Approximately 435 time stamps are stored...

Страница 41: ...ave log enables all saved values to be opened or saved in CSV format compatible with Excel type spreadsheets Clear log enables deletion of all records The administrator must enter his her login password to validate this action The card can save 435 events The table of managed alarms is included in the appendix ...

Страница 42: ...Save log enables all saved values to be opened or saved in CSV format compatible with Excel type spreadsheets Clear log enables deletion of all records The administrator must enter his her login password to validate this action The card can save 435 events The table of managed alarms is included in the appendix ...

Страница 43: ...91EN EB Page 43 118 4 3 Notification 4 3 1 Email Notification The card offers the possibility of redirecting UPS alarms to an e mail server The format of these e mails is compatible with mobile telephone transfer systems using text messages SMS ...

Страница 44: ... page will show the date and time of the next transmission Data are sent in CSV format Save Saves any modifications Test enables an e mail to be sent to the recipient immediately This is one way of checking e mail transmission particularly access to the SMTP server configured in Network settings A transmission report is added to the system log The event label in the subject and text of the message...

Страница 45: ...ation it is possible that the server checks that the domain name contained in the Sender address exists and even that the user in the Sender address belongs to this domain Subject enables the user to specify the subject of the e mail to be sent By entering some free text and selecting from several optional fields if desired the message subject is built UPS name recalls the name of the UPS it may o...

Страница 46: ...he e mail sent is composed of Message text which is free text The date and time of the event as saved in the log URL of the card enabling a direct link with the card to be established Attachments as configured for the e mail recipients duplication of the subject as configured ...

Страница 47: ...n and password are entered they remain active for 5 minutes If the browser is closed they will have to be re entered An error in either field results in systematic rejection of the requested action save page access card reboot After three unsuccessful attempts the browser must be rebooted These two fields do not travel decoded on the IT network They are encrypted with an MD5 type algorithm ensurin...

Страница 48: ... the hostname will only be sent to DNS if the DHCP server sends it the hostname with the new IP address This mechanism is described in the update of the DNS protocol RFC 2136 Domain Name is the domain to which the card belongs This is the part of the fully qualified domain name that follows the hostname and is used by the DNS The default value of the two parameters comprising the fully qualified d...

Страница 49: ...DNS Server contains the IP address of the main DNS server ensuring conversion of the domain name to IP address Secondary DNS Server contains the IP address of the secondary DNS server ensuring conversion of the domain name to IP address if the primary DNS server is not available SMTP Server contains the name or IP address of the local server with which the card connects to send e mails It may be f...

Страница 50: ...66 This text is displayed in the home page By default its value is Computer Room Default Language Enables initialisation of the browser language at card connection Choice of one of the available languages English French German Spanish Italian changes the language of the html interface pages reboot the browser after modification History log interval from 5 to 99999 sec 60 by default Measurement sav...

Страница 51: ... the default configuration of all the card s parameters TCP IP parameters IP address subnet mask gateway and BootP DHCP value are maintained if the Keep TCP IP parameters option is selected Security of this operation is ensured by requesting Login and Password The default login and password are admin admin ...

Страница 52: ...Important note It is not necessary to add the Network Shutdown Modules protecting your servers in this list These modules subscribe and unsubscribe themselves automatically Select an entry in the list to modify the values in the edit zone at the bottom of the page The table displays the following information The All button Allows the following information to be displayed Nr is the index where the ...

Страница 53: ...Two alarms Utility failure and Utility restored spaced 60 seconds apart will be sent to the applications selected making sure that the applications can be reached over the network Shutdown Test This test simulates a UPS on battery operation It enables an easy check to see if the server protection works correctly No intervention on the UPS is required The applications selected will process the simu...

Страница 54: ...he time available to the user from the power failure until the launch of the shutoff sequence of the UPS and equipment This parameter is optional Uncheck the box if you wish not to use this parameter Broadcast Sends network notifications to the Administrators and Users groups on events declared in the server hosting the NSM If you wish to set up a new configuration for the Network Shutdown Modules...

Страница 55: ...password This text field is limited to 10 characters Enables secure access to Configuration menu pages Default value admin Current Community Read name Indicates the SNMP community name used for read operations Change Community Read Only This text field is limited to 49 characters Enables the SNMP community name used for read operations to be changed Security mode manages the various authentication...

Страница 56: ... Web interface is made in secure mode https Connections with Network Shutdown Modules stay in standard mode secure TCP SSL Security Implementation SSL version 3 0 TLS version 1 0 Method TLS_RSA_WITH_512_MD5 Auth RSA Key Exchange RSA Encryption RC4_512 Digest MD5 Changes take effect after a card reboot ...

Страница 57: ... is always of year month day type Set manually Enables initialisation of the date and time of the card with the values entered in the Date and Time fields This update is made after clicking on the Save button Maximum drift is 2 min month Accept automatic update from NSM or EPM Enables initialisation of the date and time of the card with the values provide by the Network Shutdown Modules or the Ent...

Страница 58: ... are set after clicking on the Save button Time is updated every five hours thus preventing any drift in the time After two attempts if the NTP server is not accessible the card shifts to manual mode The card uses the NTP protocol UDP 123 port The firewall must be set to transmit queries outside the intranet No error message is generated if the time server contact fails Note 1 The even the card is...

Страница 59: ...Click on Firmware Upload in the menu This menu enables a new firmware version to be uploaded To upload a new version of the card s firmware select the file to be loaded using the Browse button and click Upload Do not interrupt the operation before the card displays the following screen ...

Страница 60: ...et the card 4 5 1 Characteristics Temperature measurement from 0 to 70 C with 1 C accuracy Measurement of humidity from 0 to 100 with 6 accuracy Min max time stamped function for temperature and humidity Choice of temperature readings in Celsius or Fahrenheit High and low thresholds hysteresis and offset adjustable via Web interface Possibility of notification of status changes by e mail SMS or SN...

Страница 61: ...ngs page Time stamped minimum and maximum temperatures show the extreme values recorded since the last Reset Min Max a thin dotted line shows their positions on the gauge Min and Max can be forced at any time to the current value by clicking on the Reset Min Max button Calibrate The sensor is factory calibrated but the user can apply an offset to adjust the measurement Input 1 and Input 2 show the...

Страница 62: ...ld If this value is exceeded a notification if enabled The default value is 5 C 41 F Hysteresis must be set to prevent multiple notifications if temperature fluctuates around a threshold The default value is 2 C 3 6 F The high alarm disappears when the value drops below the High threshold Hysteresis value The low alarm disappears when the value returns above the Low threshold Hysteresis value Humi...

Страница 63: ...ing functions are activated for each event selected display in the list of current alarms Consideration in the UPS log SNMP trap generation notification by e mail if the Environment sensor notification option is enabled in the e mail notification page The list of messages is given in the appendix System shutdown can be triggered for each notification if this option is enabled If notification is di...

Страница 64: ...nvironment log interval in the System settings page By default this period is 300 seconds Each measurement is dated and stored in the log of the UPS s communication card The size of log files is limited by a time indexing system The user can Save the log on his her workstation at any time in a CSV format file The user can also Clear the files contained in the card to reset the log ...

Страница 65: ...hutdown Modules connected During normal operation the protection application periodically checks its connection with the card In case of a major power event the card sends information to the protection application which reacts according to the situation shutdown order programmed actions messages to the administrator and to users via the network When the server shuts down the protection application...

Страница 66: ...hout exceeding battery backup time Note 1 The Network Shutdown Module can also manage its own Shutdown Timer configurable in the Shutdown Module set up menu of each Network Shutdown Module launched when the UPS switches to battery Note that if this criterion is selected to initiate system shutdown automatic system reboot when power is restored is not guaranteed e g power restoration if only this s...

Страница 67: ...he value set the shutdown sequence is started 5 1 1 4 Shutdown duration Duration in seconds required for the system protected by the protection application to shut down The protection application transmit their own Shutdown duration to the Network Management Card Based on these values maximum Shutdown duration of all subscribed customer systems that the card will send to the delayed shutdown order...

Страница 68: ...on outlet 1 Outlet 1 5 1 3 Protection of a server connected to a controlled outlet Network Shutdown Modules NSM starting with version 3 0 are compatible with the controlled outlets After connecting the server electrically to one of the controlled outlets the NSM must be informed of the outlet number to which it is connected Refer to the documentation of the NSM available on the internet site www m...

Страница 69: ...wn depending on its configuration The UPS restarts when utility power is restored depending on its configuration Shutdown duration Maximum value of shutdown times of protection application subscribed to the card This value is updated each time a client subscribes unsubscribes Start shutdown main output Utility failure Utility Shutdown after NSM 2 on output 1 NSM 1 on main output Shutdown duration ...

Страница 70: ... 1 5 2 3 Case of power restoration before the end of the shutdown duration counter If power is restored before the end of the Shutdown Duration the UPS is shut off after the Shutdown Duration for a time equal to the forced reboot delay 10 seconds Shutdown duration Forced Reboot Start shutdown main output Utility failure Utility Battery capacity under NSM 2 on output 1 NSM 1 on main output Main out...

Страница 71: ...elayed shutdown order to the UPS If the UPS have two NMC cards the maximum shutdown duration of the two groups of protected systems will be used for the delayed shutdown order Example If the subscribed customers of the first NMC card have a maximum Shutdown duration of 60s and the ones of the second NMC card of 120s the servers shutdown will be launched 120s before the UPS shutoff 5 3 2 Settings S...

Страница 72: ...ped with a hyperterminal type emulator The serial link must be set at 9600 baud 8 bits no parity 1 stop bit and without flow control Check that UPS power is on Enter the admin password not modifiable The menu is in English only EATON NETWORK MANAGEMENT CARD 1 Reset 2 Network configuration 3 Set Login Password to Default 4 Return to Default Configuration 0 Exit ...

Страница 73: ...application part Reset 1 Hardware Reset 2 Restart application 0 Exit 6 2 Choice 2 Network Configuration Use this function to access network settings Network settings 1 Read Network settings 2 Modify Network settings 3 Set Ethernet speed 0 Exit 6 2 1 Choice 1 Read Network settings Enables reading of the card s routine settings Network configuration MAC address 00 20 85 FD 1C 07 Mode Static IP IP ad...

Страница 74: ...tion is saved Reset the card to take into account the new configuration In DHCP mode the card can receive the following parameters according to the DHCP server settings IP address Subnet Mask Gateway address Primary DNS server Secondary DNS server The card must be restarted in order for the new parameters to be taken into account 6 2 3 Choice 3 Set Ethernet speed Enables the modification of the ne...

Страница 75: ...assword EATON NETWORK MANAGEMENT CARD 1 Reset 2 Network configuration 3 Set Login Password to Default 4 Return to Default Configuration 0 Exit Wait during Login Password return to default Wait for the confirmation message Login Password are succefully been set The card is now accessible via the Web with the password admin The card must be restarted in order for the new parameters to be taken into ...

Страница 76: ... parameters EATON NETWORK MANAGEMENT CARD 1 Reset 2 Network configuration 3 Set Login Password to Default 4 Return to Default Configuration 0 Exit Wait during configuration returns to default Wait for the confirmation message Configuration has been set to default one You must Reset the card The card must be restarted in order for the new parameters to be taken into account ...

Страница 77: ...is document The adding function consists to provide UPS Uninterruptible Power Supply data states and measures to be sent a computer system The JBUS hexadecimal MODBUS RTU communication protocol is used in slave mode The system provides a communication channel with an RS485 or RS232 interface Note 2 wires or 4 wires RS485 link are available Warning RS232 and RS485 communication ports cannot be used...

Страница 78: ...ues JBUS MODBUS communication Baud rate Parity Slave number 9600 bauds without parity Slave nr 1 1200 2400 4800 9600 Without parity even parity 1 to FF hexadecimal RS232 link Link connection in transmit data Tx or receive data Rx Rx on pin 1 Tx on pin 3 Rx on pin 1 Tx on pin 3 RS485 link Termination No termination With or without 2 or 4 wires ...

Страница 79: ...nagement Card User Manual 34003991EN EB Page 79 118 7 2 Installation 7 2 1 RS232 link configuration and connection Set the SA2 switches like below The next figure shows the details of the connection in RS232 mode ...

Страница 80: ...resistor The two ends of the line must be terminated Allow for 1 or 2 terminators to avoid mismatching the line when any equipment at the end of the line is disconnected The next figure gives the detail of the RS485 connector and the internals drivers Pin number Function 1 R Receiver input 2 R Receiver input 3 T Transmitter output 4 T Transmitter output 5 0 V Important notes Use twisted pair cable...

Страница 81: ...ugh the SA1 switches SA1 description 1 reserved 2 reserved 3 link termination between T to R 2 wires configuration if set to ON 4 connection T to R 2 wires configuration if set to ON 5 connection T to R 2 wires configuration if set to ON 6 reserved 7 reserved 8 link termination between R and R if set to ON ...

Страница 82: ...User Manual 34003991EN EB Page 82 118 7 2 2 2 RS485 link configuration for 2 wires connexion Set the SA2 switches like below to set the RS485 mode Set the SA1 switches to select the two wires configuration with no termination ...

Страница 83: ...k Management Card User Manual 34003991EN EB Page 83 118 Set the SA1 switches to select the two wires configuration with termination The next figure gives a typical bus structure in the two wires configuration ...

Страница 84: ...ement Card User Manual 34003991EN EB Page 84 118 7 2 2 3 RS485 link configuration for 4 wires connexion Set the SA2 switches like below Set the SA1 switches to select the four wires configuration with no termination ...

Страница 85: ... Management Card User Manual 34003991EN EB Page 85 118 Set the SA1 switches to select the four wires configuration with termination The next figure gives a typical bus structure in the four wires configuration ...

Страница 86: ... the cord supplied with the card Connect the card to a computer equipped with a Hyper terminal type emulator The serial link must be set at 9600 baud 8 bits no parity 1 stop bit and without flow control Check that UPS power is on Enter the admin password not modifiable Connect the RS232 link to a terminal Microsoft Hyper terminal ...

Страница 87: ...display the JBUS configuration menu The next menu appears Jbus settings 1 Display Jbus settings 2 Modify Jbus settings 3 Display Jbus diagnostics 4 Reset Jbus diagnostics 5 Return to Jbus Default Configuration 6 Display Jbus frames 0 Exit 7 2 3 1 Choice 1 Display Jbus settings Enables reading of the card s Jbus settings Jbus configuration Slave number 7 Speed 9600 bds Data 8 bits stop bit 1 Parity...

Страница 88: ...agnostics Enables reading of the Jbus diagnostics Jbus diagnostics Cpt1 Bus Message Count 0 Cpt2 CRC Error Count 0 Cpt3 Slave Exception Error Count 0 Cpt4 Slave Message Count 0 Cpt5 Slave No Response Count 0 Cpt6 Slave NAK Count 0 Cpt7 Slave Busy Count 0 Cpt8 Bus Caracter Overrun Count 0 Cpt9 Slave Correct Response Count 0 7 2 3 4 Choice 4 Reset Jbus diagnostics Reset the Jbus diagnostic counters ...

Страница 89: ...Enables the display of the Jbus frames Recv 01 01 00 00 00 64 3d e1 Send 01 81 02 c1 91 Recv 01 03 00 62 00 64 e5 ff Send 01 03 c8 00 00 00 00 00 00 00 00 00 00 00 00 00 Recv 01 01 00 00 00 64 3d e1 Send 01 81 02 c1 91 Recv 01 03 00 62 00 64 e5 ff Send 01 03 c8 00 00 00 00 00 00 00 00 00 00 00 00 00 ...

Страница 90: ...Network Management Card User Manual 34003991EN EB Page 90 118 7 3 Additional Web pages The INMC card Jbus parameters could be set through the next page ...

Страница 91: ...40 5 Low battery no yes 40 6 Operation on static switch no yes 40 7 Communication fault absent present 40 9 UPS overload no yes 40 A Emergency stop absent present 40 B Battery to be checked no yes 40 D Device ventilation fault no yes 40 E Battery present absent present 42 0 Mains 1 voltage out of tolerance no yes 44 8 Mains 1 frequency out of tolerance no yes 44 B Bypass status no yes 46 7 Charger...

Страница 92: ...ty Word hex Unit I output 109 A U output 124 V U battery 12D V Output active power 136 W Output apparent power 137 VA output load level 139 Power factor Cos PHI 13D Mains 1 frequency 13E Hz Output frequency 141 Hz Battery backup time 149 Min Battery charging level 14B U mains 1 150 V Nominal voltage of battery element 213 V ...

Страница 93: ...rgency stop absent present 40 B Battery to be checked no yes 40 D Device ventilation fault no yes 40 E Manual bypass switch Q3BP open closed 41 6 Battery present absent present 42 0 Mains 1 voltage out of tolerance no yes 44 8 Mains 1 frequency out of tolerance no yes 44 B Redundancy lost no yes 45 7 Maintenance position no yes 46 1 Mains 2 overload no yes 46 5 Output on bypass no yes 46 7 Mains 2...

Страница 94: ... I mains 2 106 A I output 109 A U mains 2 11E V U output 124 V U battery 12D V Output active power 136 W Output apparent power 137 VA output load level 139 Power factor x 100 13D Mains 1 frequency 13E dHz Output frequency 141 dHz Battery backup time 149 Min Battery charging level 14B U mains 1 150 V Nominal voltage of battery element 213 V ...

Страница 95: ...3BP open closed 41 6 UPS in eco mode no yes 41 7 Battery present absent present 42 0 Mains 1 voltage out of tolerance no yes 44 8 Mains 1 fuse fault no yes 44 9 Mains 1 frequency out of tolerance no yes 44 B Redundancy lost no yes 45 7 Maintenance position no yes 46 1 Mains 2 overload no yes 46 5 Mains 2 thermal overload no yes 46 6 Output on bypass no yes 46 7 Mains 2 frequency out of tolerance n...

Страница 96: ... A I output 109 A I battery 10E A U mains 2 11E V U output 124 V U battery 12D V Output active power 136 W Output apparent power 137 VA output load level 139 Power factor Cos PHI 13D Mains 1 frequency 13E dHz Mains 2 frequency 140 dHz Output frequency 141 dHz Battery backup time 149 Min Battery charging level 14B U mains 1 150 V Nominal voltage of battery element 213 V ...

Страница 97: ...l bypass switch Q3BP open closed 41 6 Battery present absent present 42 0 Mains 1 voltage out of tolerance no yes 44 8 Mains 1 fuse fault no yes 44 9 Mains 1 frequency out of tolerance no yes 44 B Redundancy lost no yes 45 7 Maintenance position no yes 46 1 Mains 2 overload no yes 46 5 Mains 2 thermal overload no yes 46 6 Output on bypass no yes 46 7 Mains 2 frequency out of tolerance no yes 46 9 ...

Страница 98: ...t 62 2 Inverter thermal overload Absent Present 62 3 Inverter fault Absent Present 62 4 Inverter fuse blown Absent Present 62 5 Load short circuit Absent Present 62 6 Module 2 General alarm Absent Present 63 0 Fan failure Absent Present 63 1 Internal communication fault Absent Present 63 2 Inverter thermal overload Absent Present 63 3 Inverter fault Absent Present 63 4 Inverter fuse blown Absent P...

Страница 99: ...r thermal overload Absent Present 66 3 Inverter fault Absent Present 66 4 Inverter fuse blown Absent Present 66 5 Load short circuit Absent Present 66 6 Module 6 General alarm Absent Present 67 0 Fan failure Absent Present 67 1 Internal communication fault Absent Present 67 2 Inverter thermal overload Absent Present 67 3 Inverter fault Absent Present 67 4 Inverter fuse blown Absent Present 67 5 Lo...

Страница 100: ... V U12 mains 2 121 V U23 mains 2 122 V U31 mains 2 123 V U1N output 124 V U2N output 125 V U3N output 126 V U12 output 127 V U23 output 128 V U31 output 129 V U battery 12D V Output active power phase 1 130 W Output active power phase 2 131 W Output active power phase 3 132 W Output apparent power phase 1 133 VA Output apparent power phase 2 134 VA Output apparent power phase 3 135 VA Output total...

Страница 101: ...gement Card User Manual 34003991EN EB Page 101 118 Description of the physical quantity Word hex Unit U mains 1 phase 1 150 V U mains 1 phase 2 151 V U mains 1 phase 3 152 V Nominal voltage of battery element 213 V ...

Страница 102: ...on Status to 0 Status to 1 Word hex Bit Input 1 alarm no yes 45 5 Input 2 alarm no yes 45 6 Alarm humidity too low no yes 45 4 Alarm humidity too high no yes 45 3 Alarm temperature too low no yes 45 2 Alarm temperature too high no yes 45 1 Communication fault no yes 45 0 Input 1 open close 48 0 Input 2 open close 48 1 ...

Страница 103: ...emperature date MSB in Unix timestamp 185 Minimum temperature date LSB in Unix timestamp 186 Humidity measure 187 Maximum humidity 188 Maximum humidity date MSB in Unix timestamp 189 Maximum humidity date LSB in Unix timestamp 190 Minimum humidity 18B Minimum humidity date MSB in Unix timestamp 192 Minimum humidity date LSB in Unix timestamp 193 Input 1 changing date MSB in Unix timestamp 194 Inpu...

Страница 104: ...31 0 Humidity hysteresis 332 0 Humidity offset 333 0 Inputs call mask input 1 close notification 334 0 Inputs call mask input 2 close notification 334 2 Inputs call mask low humidity notification 334 7 Inputs call mask high humidity notification 334 6 Inputs call mask input 1 open notification 334 1 Inputs call mask input 2 open notification 334 3 Inputs call mask low temperature notification 334 ...

Страница 105: ...ard User Manual 34003991EN EB Page 105 118 7 4 6 Other data Information description Word hex Example Manufacturer name 1A0 MGE Office Protection Systems Product name 1A8 Pulsar UPS model 1B0 700 Serial number 1B8 AN2E49008 ...

Страница 106: ...K Bypass AC frequency out of tolerance Bypass AC frequency OK Bypass AC phase out of tolerance Bypass AC phase OK Bypass AC voltage out of tolerance Bypass AC voltage OK Automatic Bypass fault Automatic Bypass OK Automatic Bypass overload Automatic Bypass load OK Automatic Bypass overtemperature Automatic Bypass temperature OK Automatic Bypass thermal overload Automatic Bypass load OK Automatic By...

Страница 107: ... UPS returns to normal load UPS overtemperature UPS temperature OK Imminent UPS shutoff UPS OK Sensor name Temperature is above high threshold xx C Sensor name La température est au dessus du seuil haut xx C Sensor name Humidity is above high threshold xx Sensor name L humidité est au dessus du seuil haut xx Sensor name Temperature is below low threshold xx C Sensor name La température est en dess...

Страница 108: ...Normal AC frequency OK Normal AC voltage out of tolerance Normal AC voltage OK Normal AC switch Q1 open Normal AC switch Q1 closed Site wiring fault Site wiring OK Automatic Bypass switch Q4S open Automatic Bypass switch Q4S closed Bypass AC frequency out of tolerance Bypass AC frequency OK Automatic Bypass fault Automatic Bypass OK Automatic Bypass overload Automatic Bypass load OK Automatic Bypa...

Страница 109: ...t 2 open Outlet 2 closed Chopper fault Chopper OK Normal AC switch Q1 open Normal AC switch Q1 closed Normal AC frequency out of tolerance Normal AC frequency OK Normal AC fuses blown Normal AC fuses OK Normal AC module fault Normal AC module OK Normal AC voltage out of tolerance Normal AC voltage OK Site wiring fault Site wiring OK Automatic Bypass switch Q4S open Automatic Bypass switch Q4S clos...

Страница 110: ... communication restored UPS data base not available UPS data base OK UPS on battery UPS on normal AC Emergency button ON Emergency button OFF Fan fault Fan OK Load not powered Load powered UPS internal fault UPS OK Battery fault Battery OK UPS overload UPS returns to normal load UPS overtemperature UPS temperature OK Imminent UPS shutoff UPS OK Sensor Name Temperature is above high threshold xx C ...

Страница 111: ...ail ERROR Send mail to recipient ERROR Sensor name Communication failure Sensor name Communication restored Firmware upgraded Connected NSM list Full last connection refused sendTrap Unable to resolve hostname hostname SNMP Send Trap num failure to hostname Time changed by user with yyyy mm dd hh mm ss Time synchronized by NSM or EPM with yyyy mm dd hh mm ss ...

Страница 112: ...rrent deciAmps 5 6 0 upsmgBatteryFaultBattery 1 yes 2 no 5 9 0 upsmgBatteryReplacement 1 yes 2 no 5 11 0 upsmgBatteryLowBattery 1 yes 2 no 5 14 0 upsmgBatteryChargerFault 1 yes 2 no 5 15 0 upsmgBatteryLowCondition 1 yes 2 no 5 16 0 upsmgInputPhaseNum 6 1 0 mginputVoltage_1 DeciVolts 6 2 1 2 1 0 mginputVoltage_2 DeciVolts 6 2 1 2 2 0 mginputVoltage_3 DeciVolts 6 2 1 2 3 0 mginputFrequency_1 DeciHz ...

Страница 113: ... 5 1 0 mgoutputCurrent_2 deciAmps 7 2 1 5 2 0 mgoutputCurrent_3 deciAmps 7 2 1 5 3 0 upsmgOutputOnBattery 1 yes 2 no 7 3 0 upsmgOutputOnByPass 1 yes 2 no 7 4 0 upsmgOutputUtilityOff 1 yes 2 no 7 7 0 upsmgOutputInverterOff 1 yes 2 no 7 9 0 upsmgOutputOverLoad 1 yes 2 no 7 10 0 upsmgOutputOverTemp 1 yes 2 no 7 11 0 upsmgAgentIpAddress 12 1 0 upsmgAgentSubnetMask 12 2 0 upsmgAgentDefGateway 12 3 0 up...

Страница 114: ...dex 8 7 1 1 1 upsmgEnvironmentComFailure 1 yes 2 no 8 7 1 2 1 upsmgEnvironmentTemperature 0 1 degré 8 7 1 3 1 upsmgEnvironmentTemperatureLo w 1 yes 2 no 8 7 1 4 1 upsmgEnvironmentTemperatureHi gh 1 yes 2 no 8 7 1 5 1 upsmgEnvironmentHumidity 0 1 8 7 1 6 1 upsmgEnvironmentHumidityLow 1 yes 2 no 8 7 1 7 1 upsmgEnvironmentHumidityHigh 1 yes 2 no 8 7 1 8 1 upsmgEnvironmentInput1State closed 1 open 2 8...

Страница 115: ...el 3 upsmgLoadOK Trap 22 Level 1 upsmgOverTemperature Trap 23 Level 3 upsmgTemperatureOK Trap 24 Level 1 upsmgOffToStart Trap 29 Level 2 upsmgOffInProgress Trap 31 Level 3 upsmgCommunicationFailure Trap 37 Level 3 upsmgCommunicationRestored Trap 38 Level 1 upsmgRedundancyLost Trap 65 Level 2 upsmgRedundancyOK Trap 66 Level 2 upsmgProtectionLost Trap 67 Level 2 upsmgProtectionOK Trap 68 Level 2 If ...

Страница 116: ...6 118 upsEnvironmentInput1Open Trap 62 Level 2 upsEnvironmentInput2Open Trap 64 Level 2 upsEnvironmentInput2Closed Trap 63 Level 2 The level is used to select traps to be sent to the supervisor This adjustment is available from the Notified applications page ...

Страница 117: ...web HTTPS is the secure version of HTTP the communication protocol of the World Wide Web It was invented by Netscape Communications Corporation to provide authentication and encrypted communication and is used in electronic commerce IP Internet Protocol Network layer protocol in the TCP IP stack offering a no connection inter network service The IP protocol offers functions for addressing service ...

Страница 118: ...ministrate and control devices connected to a company network SMTP SIMPLE MAIL TRANSFER PROTOCOL Enables message transfer between e mail servers or between the client and its server It is based on the server s port 25 It is described in RFC 821 SSL Secure Sockets Layers is a protocol developed by Netscape Communications Corporation for securing data transmission in commercial transactions on the I...

Отзывы: