8
200 A Fused Loadbreak Elbow Connector Replacement Fuse
InstallatIon InstructIons
MN132021EN November 2016
Elbow Housing and Probe Reassembly
Step 14
IMPORTANT
Align the flats of the probe adapter parallel to the nosepiece
of the bushing.
Assemble set screws into the probe adapter.
Using supplied 1/8
"
(3 mm) hex wrench, thread the two set
screws until they bottom out on the end post of the fuse,
then tighten each set screw an additional 1/8 - 1/4 turn until
tight.
Probe Adapter
Seated Flush On Top
of Fuse End Cap
1/8" (3mm)
Hex Wrench
Align the Flats
of the Probe
Adapter
Parallel to the
Nosepiece of
the Bushing
Loadbreak
Bushing Insert
Step 15
Using supplied lubricant, clean and lubricate elbow and
cable interfaces.
Assemble elbow housing onto the cable housing. Make
sure the test point is facing outward away from the front
plate of the apparatus.
Insert Elbow
Clean and Lubricate
Interfaces with
Supplied Lubricant
Facing Outward