IB131006EN
Page 3
Effective 07/2017
Table 1.2 (ANSI Standards
) Type VCP-W Vacuum Circuit Breaker 27 kV Rated Symmetrical Current Basis
Identification
Rated Values
Circuit
Breaker
Type
Nominal
Voltage
Class
Nominal
3-Phase
MVA
Class
Voltage
Insulation Level
Current
Inter-
rupting
Time
Permis-
sible
Tripping
Delay
Y
Transient Recovery Voltage Current Values
Maximum
Voltage
E
Voltage
Range
Factor
K
Withstand Test
Voltage
Continuous
Current
at 60 Hz
Short
Circuit
Current
3 Second
Short time
Current
Carrying
Capability
I
E
2
t
2
Rise
Time
Closing
and
Latching
Capability
2.7 K
Times
Rated
Short
Circuit
Current
Capacitor
Switching
Cable
Charging
Power
Frequency
(1 Min.)
Impulse
kV
MVA
kV rms
kV rms
Amperes
kA rms
Cycles
Seconds kV rms
kA rms
kA Peak
kA rms
270VCP-W750
( 1 6 )
( A )
27
750
27
1.0
60
125
600
1200
2000
16
5
2
51
105
43
31.5
270VCP-W1000
( 2 2 )
( A )
27
1000
27
1.0
60
125
600
1200
2000
22
5
2
51
105
60
31.5
270VCP-W1250
( 2 5 )
( A )
27
1250
27
1.0
60
125
600
1200
2000
25
5
2
51
105
68
31.5
270VCP-W1600
( 3 2 )
27
1600
27
1.0
60
125
1200
2000
31.5
5
2
51
105
85
31.5
270VCP-W2000
( 4 0 )
( B )
27
2000
27
1.0
60
125
1200
2000
40
5
2
51
105
106
31.5
CESI tested to applicable ANSI Standards C37.04 - 1979, C37.09 - 1979, and
C37.06 -199X. Consult Eaton for CESI reports on file. Operating duty
cycle CO-15 seconds-CO. Operating time values: opening 33-55 ms,
closing 50-60 ms and reclosing 18 cycles (300 ms).
(A)
Tested at 28.5kV RMS. (B) Tested at 29.2kV RMS.
K=1.0, therefore E = E/K and I = KI. Consult Application Data 32-265 for further
information.
Optional interrupting time of 3 cycles is available.
Also maximum interrupting rating.
Table 1.3 (ANSI Standards) Type VCP-WC Extra Capability Vacuum Circuit Breaker 5-27 kV Rated Symmetrical
Current Basis
Identification
Rated voltage
Circuit
Breaker
Type
Voltage
Insulation level
Inter-
rupting
Time
(1)
Maximum
Permissible
Tripping
Delay
Transient
Recovery
Voltage
(RRRV)
Capacitor Switching Ratings
Mechanical
Endurance
No-load
Operations
Max
Voltage
V
Voltage
Range
factor
K
Withstand test
Short Circuit Current
General
Purpose
Definite Purpose
Power
Frequency
(1 Min.)
Lightening
Impulse
1.2x50us
Continuous
Current at
60 Hz
Sym.
Inter-
rupting
at V (Isc)
% dc
compo-
nent
(Idc)
Asym.
Inter-
rupting
(It)
Closing
&
Latching
Capa-
bility
Short-
Time
Current
for
3 sec.
Isolated
Shunt
Capacitor
Bank
Current
Back to Back Capacitor Switching
Capacitor
Bank
Current
Inrush
Current
Inrush
Frequency
(3)
KV rms
kV rms kV Peak
A rms
kA rms
Total
%
kA rms kA Peak kA rms Ms
Seconds kV / µs
A rms
A rms
kA Peak
kHz
50 VCP-W 40C
5.95
1
24
75
1200
2000
3000
40 75 58 139 40 50 2
0.9
0.9
0.8
630 (5)
1000 (5)
—
15
18
—
3.5
2.7
—
10,000
10,000
5,000
50 VCP-W 50C
5.95
1
24
75
1200
2000
3000
50
57
57
52
64
64
62
139 50 50 2
0.9
0.9
0.8
630 (5)
1000 (5)
—
15
18
—
3.5
2.7
—
10,000
10,000
5,000
75 VCP-W 50C
10.3
1
42
95
1200
2000
3000
50
57
57
52
64
64
62
139 50 50 2
0.9
0.9
0.8
630 (5)
1000 (5)
—
15
18
—
3.5
2.7
—
10,000
10,000
5,000
150 VCP-W 25C
17.5
1
42
95
1200
2000
3000
25
50
75
75
31
36
36
97 (2)
25
50
2
0.95
0.9
0.8
600 (6)
1000 (5)(6)
—
20
18
—
3.5
2.7
—
10,000
10,000
5,000
150 VCP-W 40C
17.5
1
42
95
1200
2000
3000
40 75 58 139 40 50 2
0.9
0.9
0.8
630 (4)
630 (4)
250 (4)
630 (5)(6)
1000 (5)(6)
—
15
18
—
3.5
2.7
—
10,000
10,000
5,000
150 VCP-W 50C
17.5
1
42
95
1200
2000
3000
50
57
57
52
64
64
62
139 50 50 2
0.9
0.9
0.8
630 (4)
630 (4)
250 (4)
630 (5)(6)
1000 (5)(6)
—
15
18
—
3.5
2.7
—
10,000
10,000
5,000
150 VCP-W 63C
17.5
1
42
95
1200
2000
3000
63
61
61
61
83
83
83
175 63 50 2
1.07
1.07
1.07
200,1600(9)
200,1600(9)
200,1600(9)
7.7
7.7
7.7
465
465
465
10,000
10,000
10,000
270 VCP-W 25C
(A)
27 1 60 125 1200
1600
25 75 36 85 25
(8)
50 2 1.1
400
20 4.2 2,500
270 VCP-W 32C
27 1 60 125 1200
1600
31.5 57 40 97 32
(7) 50 1
1.1
400
20 4.2 2,500
270 VCP-W 40C
(B)
27 1 60 125
1200
1600
40 50 49 104
40
(7)
50 1 1.1
400
20 4.2 2,500
(1) 3 cycles
(2) Close & Latch Current for 1 200A Type 150 VCP-W 25C is proven at
15kV. For sealed interrupters at high altitudes, switching voltage is
not de-rated.
(3) For higher RRRV contact Eaton for more information.
(4) Breaker tested to 2700A single bank switching for momentary
load (Thermal derating must consider harmonic content of
current waveform).
(5) Breaker tested to 1 270A back-to-back switching for momentary
load (Thermal derating must consider harmonic content of
Current waveform)
(6) Capacitor Switching Ratings are proven at 15kV. For sealed
interrupters at high altitudes, switching voltage is not de-rated.
(7) 1 second
(8) 2 second
(9) C37.04a-2003 Class C2 @ 15kV
Содержание 120VCP-W25
Страница 28: ...IB131006EN Page 22 Effective 07 2017 position Courtesy of NationalSwitchgear com ...
Страница 40: ...IB131006EN Page 34 Effective 07 2017 Figure 5 4 charging schematic Courtesy of NationalSwitchgear com ...
Страница 44: ...IB131006EN Page 38 Effective 07 2017 Figure 5 5A CONTINUED Courtesy of NationalSwitchgear com ...
Страница 65: ...IB131006EN Page 59 Effective 07 2017 Courtesy of NationalSwitchgear com ...
Страница 67: ...IB131006EN Page 61 Effective 07 2017 Courtesy of NationalSwitchgear com ...