6-11 TROUBLESHOOTING CHART (Continued Next Page)
SYMPTOM
INSPECTION AREA
PROBABLE DEFECTS
Fails To Close
• Closing Sound
but no close
• Pole
Shaft
(Not open fully)
• Trip Latch Reset Spring
(Damaged or Missing)
• Trip Bar-D Shaft
(Fails to remain reset)
• Trip Latch-Hatchet
(Fails to remain reset)
• Trip
Floor
Tripper
(Fails to remain reset)
• Close Latch
(Binding)
• Close
Latch
Roller
(Binding)
• Trip Circuit Energized
Undesirably Closes
•
Control Circuit
• Close
Circuit
(CS/C Getting Shorted)
• Mechanism
• Close Release Latch
(Fails to reset)
• Close Floor Tripper
(Fails to reset)
Fails To Trip
• No Trip Sound
• Control
Circuit
• Control Power
(Fuse blown or switch off)
• Secondary Disconnect
• Auxiliary Switch
(a contact not making, poor or burned)
• Trip
Coil
(Burned or open)
• Terminals and Connections
(Poor or burned or open)
• Trip Mechanism
• Trip Clapper
(Jammed)