CCA-410-IM (03/15)
Page 13
For horizontal cased coil applications (left or right air flow), the TXV control box is field positioned
external to the cased coil and can be fastened to a solid mounting surface immediately adjacent to the
cased coil as shown typically in Figure 8b.
Figure 8b. TXV Control installed near Cased Coil (Horizontal Application)
Important!
The TXV control box must be located no more than 3-1/2 feet from the
suction tube stub out on the cased coil. The TXV control box must be
mounted above the cased coil tubing stub outs as shown.