PLANNING YOUR INSTALLATION
PAGE 5
COMBUSTIBLE WALL CLEARANCE
WARNING: IT IS VERY IMPORTANT THAT YOU
OBSERVE THE MINIMUM CLEARANCES.
There are listed clearances for your stove which were
determined in a Laboratory test using various "classes"
of stove pipe or chimney. Minimums are first estab-
lished for the stove itself and increased based on how
much heat is transferred by each class of pipe.
Note: Manufactured (mobile) home installations require
the use of a Type L Vent Chimney connector only. Use
of a single wall flue pipe connection is not permitted.
Residential Reduced Clearance
Using Listed L Vent pipe (double wall air insulated) to
the top of the stove.
Approved brands are: Jakes-Evans, Dura-Vent, Secu-
rity, Pro-Vent, Ameri-Tek, Metal Bestos.
Clearances (inches / millimeters)
A. 10 ½ / 267
C. 15 / 381
E. 9 ½ / 241
B. 20 / 508
D. 8 / 203
F. 5 / 127
Residential Standard
(not approved for manufac-
tured [mobile] homes)
Using single wall pipe connector to the top of the stove.
Clearances (inches / millimeters)
A. 15 / 381
C. 15 / 381
E. 8 ½ / 216
B. 19 / 483
D. 13 / 330
F. 5 / 127
Manufactured (Mobile) Home Standard Clearance
Using Approved L Vent only. Approved brands are
Dura-Vent, Security, Pro-Vent, and Ameri-Tek. Manu-
factured (mobile) Home installations must use a rain
cap with a spark arrestor.
Clearances (inches / millimeters)
A. 10 ½ / 267
C. 15 / 381
E. 9 ½ / 241
B. 20 / 508
D. 8 / 203
F. 5 / 127
CORNER
INSTALLATION
PARALLEL
INSTALLATION
*ALCOVE CLEARANCE
Required pipe: Type L-Vent pipe to top of stove. Ap-
proved brands are Dura-Vent, Pro-Vent, Ameri-I-Tek,
Standex, and Metal Bestos.
Alcoves must have minimum
dimensions of 84" (213
cm) height minimum, 46" (117 cm) width minimum and
24" (610 mm) depth maximum.
Alcove Clearances:
Back wall to pipe O.D.
10 1/2" (267 mm) Minimum
Side wall to pipe O.D.
20" (508 mm) Minimum
Back wall to stove
8" (203 mm) Minimum
Side wall to stove
9 1/2" (241 mm) Minimum
* NOTE:
Alcove dimensions cannot be reduced by the use of
non-combustible materials such as brick, stone, etc. Alcove
dimensions listed are minimum dimensions and are not
measurements for building an Alcove. You will need to con-
sider these clearances, as well as other dimensional re-
quirements before you build the alcove and install this appli-
ance.
PROTECTED WALL CLEARANCE
when the stove is in-
stalled adjacent to a protected wall system. The variance must
be approved by your local building official. Normally, the pro-
tected wall system is defined as a non- combustible material
with a minimum of 1" air space behind. Check your local build-
ing codes or with a qualified installer (Ref. NFPA 211).
OPTIONAL ARCH TREATMENT
An alcove depth of 24" (610 mm) (or less) will allow for a
minimum height of 84" (213 cm) and may be trimmed with a 2
1/4" (57 mm) maximum arch treatment if desired.
Содержание EARTHSTOVE 1500HT
Страница 24: ...SAFETY LISTING LABEL PAGE 24...
Страница 25: ...EPA LABEL PAGE 25...
Страница 27: ...1110 West Taft Avenue Orange CA 92865...