PLANNING YOUR INSTALLATION

PAGE 7

FACTORY BUILT FIREPLACES

This appliance is approved for installation into a listed factory
built solid fuel burning fireplace. The fireplace firebox must
accept the insert without modification other than re-
moving bolted or screwed together pieces such as
smoke shelf/deflectors, ash lips, screen or door tracks
and damper assemblies, that must be reinstalled to re-
store the fireplace to its original operating condition if
the insert is removed and not replaced.  The removal of
any part must not alter the integrity or outer shell of the
pre-engineered fireplace cabinet in any way.

Venting Requirements for factory built fireplace:

The fireplace damper must be secured in the open position.
This appliance requires the use of a 6” diameter flex or
rigid, UL1777 listed 2100

°

 HT liner or equivalent. The

liner must extend from the flue outlet of the appliance to
termination. Do not face seal over fireplace chimney
cooling air systems. Offsets can be handled with an offset
adapter (it aligns starter pipe with fireplace flue).  For more
information on the offset adapter, see pages 9 and 25.

WARNING: Do not substitute the heat rated
2100

°°°°

HT liner with any other type line or a fire

may result causing property damage, personal
injury or loss of life.

MASONRY FIREPLACES

This appliance is approved for installation into a masonry
fireplace built to UBC Chapter 37 standards. Do not remove
brick or mortar form the masonry fireplace to accommodate
this appliance.

Venting Requirements for masonry fireplace:

The fireplace damper must be secured in the open position.
As a minimum, a flue extension past the fireplace header is
required.  A preferred installation is a positive flue connection
(sealing the throat of the chimney). This appliance requires
the use of a 6” diameter flex or rigid single wall pipe,
minimum 24/25 MSG black or blued steel connector
pipe (stainless steel recommended). Offsets can be han-
dled with an offset adapter (it aligns starter pipe with fireplace
flue).  For more information on the offset adapter, see pages
9 and 25.

FIREPLACE CHIMNEY MAXIMUM SIZE TO ENSURE
PROPER DRAFT

The fireplace insert flue size is 6 inches diameter, which
is approximately 28 square inches, the minimum. The
maximum flue size should be no more than (3) three
times the cross sectional area of the size of the fireplace
insert flue collar. In this case, that would be no larger
than a 10 inch diameter stack (area = approx. 85 sq.
inches).

Note: Formulas for calculating area:

Calculating area of a circle:

π

 x r

2  

= Area (

π

 = 3.1416, r = 1/2 diameter)

To calculate area of square or rectangle:
Width x Depth = Area

Notes:

!

 

It may be necessary to use a full-length liner to
achieve adequate draft for the appliance. A draft
gauge should read more than .04 W.C.I, but less
than .08 W.C.I. for optimum performance

.

!

 

This appliance is approved for all heatform style
fireplaces (masonry fireplace with a metal fire-
box liner).

!

 

Measure fireplace size to make certain the insert will
fit before considering the installation.

.

Содержание BV4000C

Страница 1: ...FIREPLACE INSERT MODEL BV4000C P N 775006M Rev J 04 01 THIS APPLIANCE MUST BE INSTALLED BY A QUALIFIED TECHNICIAN READ MANUAL THOROUGHLY BEFORE INSTALLATION RETAIN THESE INSTRUCTIONS FOR FUTURE REFERE...

Страница 2: ...ay from the heater while it is in use 12 DO NOT OVERFIRE If heater or chimney con nector glows you are overfiring Overfiring this ap pliance could cause a house fire Overfiring is a condition where th...

Страница 3: ...r temperature probe and sleeve One Damper Hook USING THIS MANUAL Please read and carefully follow all of the instructions found in this manual Please pay special attention to the safety instructions p...

Страница 4: ...EC ANSI NFPA 70 1987 In Canada CSA C22 1 WARNING Electrical Grounding Instruc tions This appliance is equipped with a three prong grounding plug for your protection against shock hazard and should be...

Страница 5: ...r protection equivalents To determine the thickness required for any material when either the k or r values are known TM Thickness of material in inches KM K value of desired material TL Minimum liste...

Страница 6: ...himney may require a liner to improve performance CLEARANCES WARNING It is very important that you observe the minimum clearances There are listed clearances for your fireplace insert which were deter...

Страница 7: ...Do not remove brick or mortar form the masonry fireplace to accommodate this appliance Venting Requirements for masonry fireplace The fireplace damper must be secured in the open position As a minimu...

Страница 8: ...sleeve It may be necessary to bend the flange on the plug so it won t interfere with the probe temperature indicator The Catalytic Temperature Probe is provided so you can monitor the temperature of y...

Страница 9: ...e or positive flue connection a minimum of a 6 starter pipe extending past the header is required See note 9 Factory Built Fireplace Slide insert into the fireplace far enough to attach connector to f...

Страница 10: ...the face shield and stove Push the unit back until face shield insulation is com pressed against the fireplace front forming a tight seal Test for air leaks by holding a candle around edge of face sh...

Страница 11: ...Or Install 6 flex pipe to achieve the same result Use an offset adapter see page 25 to handle offsets This part is available through your dealer A preferable installation is the positive flue connect...

Страница 12: ...t will affect the control setting The same control settings in a variety of installations will produce different results You will need to try different settings so you can learn how much heat to expec...

Страница 13: ...stove burning with the door ajar or open Leav ing the door ajar or open while the stove is burning will cause excessive heat build up in the stove overfiring and could ignite surrounding combustibles...

Страница 14: ...600 F During the refueling we recommend that the stove be refired for about 10 minutes with the bypass open to ensure a good draw is established and that the catalyst reaches 600 F The refiring will e...

Страница 15: ...ded periods without running the blowers can cause excessive temperatures resulting in overfir ing damage to the appliance Excessive heat will cause the propellers on the blowers to melt If this occurs...

Страница 16: ...TIC TEMPERATURE PROBE The catalytic temperature probe monitors the tempera ture of your catalytic combustor Once you have estab lished a fire and the catalytic temperature probe indi cates the tempera...

Страница 17: ...be stacked in an area open enough to ensure good air circulation on both sides leaving adequate space between woodpiles to walk comfortable Do not stack wood against a wall or building It helps to el...

Страница 18: ...re installations using this type of flue are more susceptible to creosote de posits To inhibit the build up of creosote adjust the primary air control to a medium high or high setting for a 10 minute...

Страница 19: ...distilled water for 30 minutes Then rinse by soaking in hot distilled water After 15 minutes remove the com bustor from the rinse water and gently shake out excess water It is unlikely that you will n...

Страница 20: ...based on average climates and home design 5 There s an obstruction in the chimney 6 The chimney or chimney cap is restricted by creosote preventing enough draw to sustain a HIGH heat rate 7 Combustor...

Страница 21: ...imited warranty The following are a few conditions that should be evaluated and corrected if necessary if an overfiring condition is suspected Overfiring Caused From Improper Installation The venting...

Страница 22: ...ity 70 lbs approx Firebox size cubic feet 2 4 c f Maximum Burn Rate 56 800 BTU EPA BTU Range 6 500 to 40 900 BTU EPA Efficiency 72 Emissions Rate grams hour 1 9 gph Approx weight with brick 390 lbs Ai...

Страница 23: ...Torque plate nut ELECTRICAL PARTS Part Catalog Description Notes 4020 Blower assembly includes 2 blowers propellers mounting bracket termi nal block 11573 Blower axial 13 1 4 J239 5116 42amps Includes...

Страница 24: ...MPONENT DIAGRAMS Model BV4000C PAGE 24 DAMPER ASSEMBLY CATALYTIC DAMPER COMPONENTS PRIMARY AIR CONTROL DRAFT MODULE PART CATALOG 11493 DOOR ASSEMBLY PART CATALOG G3000 HANDLE ASSEMBLY PART CATALOG 103...

Страница 25: ...ORD CHANGEOVER KIT The blower system can be easily transferred to the other side of the stove along with the power cord by installing this cord changeover kit This kit consists of a reversed right and...

Страница 26: ...SAFETY LISTING LABEL EPA LABEL PAGE 26...

Страница 27: ...SERVICE AND MAINTENANCE LOG Service Service Service Date Technician Description PAGE 27...

Страница 28: ...1110 West Taft Avenue Orange CA 92865...

Отзывы: