Water Sensing Cable

LP-LPD Water Leak Locating Panel Quick Start Guide

Page 1 of 10

LP-LPD Water Leak Locating Panel

Quick Start Guide

General Note

To ensure normal operation, please follow thru various instructions listed in this manual.

The LP-LPD water leak locating panel is designed to detect liquid leak of the sensing cable up to 900m.
Once liquid leak is detected, the LP-LPD water leak locating panel gives an audible and visual alarm, also,
a 7-Segment LED will indicate the leak location and the relay output is energized. The communication
Protocol of LP-LPD water leak locating panel is Modbus RTU which is easy to interface with BMS
systems.
LP-LPD can be either stand alone or interfacing with the BMS system.
Its application includes Data Centre, Warehouse, library, museum and so on.

Product Features:

LED light shows Power, Leak, Cable Fault, and Communication Status

The LED display shows leak location and cable fault.

32 leak alarm records can be stored

Serial RS-485 communication Port with Modbus Protocol

12V DC power supply.

NO/NC Relay output is available

Din rail installation

86*70*58 mm in size

Содержание LP-LPD

Страница 1: ...ment LED will indicate the leak location and the relay output is energized The communication Protocol of LP LPD water leak locating panel is Modbus RTU which is easy to interface with BMS systems LP L...

Страница 2: ...0 140 Operating temperature 0 45 32 117 Humidity 5 95 Non condensing Power Requirements LP LPD 12VDC 3W Serial Interface Network Configuration RS 485Serial port different baud rates are available and...

Страница 3: ...hanical shock and impact Keep dry Avoid electrostatic discharge to the panel Prevent the contact with metal filings grease pipe coatings and other contaminants Installation Diagram Installation of LP...

Страница 4: ...n digital signal for any BMS system Wiring Combination Alarm Status Output State N O COM No alarm Open Alarm Closed Loss of power Open N C COM No alarm Closed Alarm Open Loss of power Closed Connectio...

Страница 5: ...tem LP LPD panel must be assigned address The factory default address of all LP LPDs is 0 and its baud rate is 9 600 Each LP LPD must be an unique address and same communication baud rate Please follo...

Страница 6: ...as click Settings respectively When the baud rate and communication address are successfully set up it means the setup is finished It is worth noting that the settings will not change unless the LP L...

Страница 7: ...leak sensing cable to the termination take measurement of the resistance between the yellow and black cables with the ohms range of multimeter after the connection between lead out wire and leak sens...

Страница 8: ...box You can also enter the desired time into the clock display box and click Write into Module to correctly set the LP LPD time Maintenance Troubleshooting Each Panel is well tested before shipment St...

Страница 9: ...n TX TRANSMIT RX RECEIVE State Flash Flash The LP LPD normally communicates with Master OFF Flash The LP LPD receives information from the Master and no message back OFF Normally ON The RS485 communic...

Страница 10: ...ed properly If leak location is not accurate This may probably due to small amount of liquid still exists at different points on the sensing cable Also it can be due to some contamination with electro...