Water Sensing Cable

LP-LPD Water Leak Locating Panel Quick Start Guide

Page 9 of 10

Table 1. LED Indication of the Running Status of LP-LPD

Power indicator (red)

ON

Normal power-on

OFF

Abnormal power or fault of LP-LPD

Disconnection

indicator (green)

ON

Fault or improper connection of leak sensing cable

OFF

Proper connection of leak sensing cable

Leak indicator

(green)

ON

Leak

OFF

There is no leak

Table 2. LP-LPD Communication Status Indication

TX (TRANSMIT)

RX (RECEIVE)

State

Flash

Flash

The LP-LPD normally communicates with Master

OFF

Flash

The LP-LPD receives information from the Master and no

message back

OFF

Normally ON

The RS485 communication cable is reversely installed or the

communication chip malfunctions

OFF

OFF

The LP-LPD does not communicate with the master

Liquid leakage is detected when there is no obvious liquid presence. The possible reasons are as
follows (it is highly recommended to replace the affected section):

1. The sensing cable was badly contaminated by some chemical for unknown reason.
2. The sensing cable was coated with glue, epoxy and paint accidentally.

Содержание LP-LPD

Страница 1: ...ment LED will indicate the leak location and the relay output is energized The communication Protocol of LP LPD water leak locating panel is Modbus RTU which is easy to interface with BMS systems LP L...

Страница 2: ...0 140 Operating temperature 0 45 32 117 Humidity 5 95 Non condensing Power Requirements LP LPD 12VDC 3W Serial Interface Network Configuration RS 485Serial port different baud rates are available and...

Страница 3: ...hanical shock and impact Keep dry Avoid electrostatic discharge to the panel Prevent the contact with metal filings grease pipe coatings and other contaminants Installation Diagram Installation of LP...

Страница 4: ...n digital signal for any BMS system Wiring Combination Alarm Status Output State N O COM No alarm Open Alarm Closed Loss of power Open N C COM No alarm Closed Alarm Open Loss of power Closed Connectio...

Страница 5: ...tem LP LPD panel must be assigned address The factory default address of all LP LPDs is 0 and its baud rate is 9 600 Each LP LPD must be an unique address and same communication baud rate Please follo...

Страница 6: ...as click Settings respectively When the baud rate and communication address are successfully set up it means the setup is finished It is worth noting that the settings will not change unless the LP L...

Страница 7: ...leak sensing cable to the termination take measurement of the resistance between the yellow and black cables with the ohms range of multimeter after the connection between lead out wire and leak sens...

Страница 8: ...box You can also enter the desired time into the clock display box and click Write into Module to correctly set the LP LPD time Maintenance Troubleshooting Each Panel is well tested before shipment St...

Страница 9: ...n TX TRANSMIT RX RECEIVE State Flash Flash The LP LPD normally communicates with Master OFF Flash The LP LPD receives information from the Master and no message back OFF Normally ON The RS485 communic...

Страница 10: ...ed properly If leak location is not accurate This may probably due to small amount of liquid still exists at different points on the sensing cable Also it can be due to some contamination with electro...