EC590
Function parameters description
EC590
Function parameters description
-
91
-
-
92
-
Function
Code
Function definition
Parameter description
Default
Setting Range
F7-04
LED display
running
parameters 2
0
0000~FFFF
0000 to FFFF
BIT0:PID feedback
BIT1:PLC stage
BIT2:Pulse reference(kHz)
BIT3:Running frequency 2(Hz)
BIT4:Remaining running time
BIT5:AI1 voltage before correction(V)
BIT6:AI2 voltage before correction(V)
BIT7:Keyboard potentiometer voltage
before correction
BIT8:Linear speed
BIT9:currentpower-on time(h)
BIT10:currentpower running time(Min)
BIT11:Pulse reference(Hz)
BIT12:Communication reference
BIT13:Enceder feedback speed(Hz)
BIT14:Main frequency X display(Hz)
BIT15:Auxiliary frequency Y display(Hz)
F7-05
Display stop
parameter
33
0000~FFFF
0000 to FFFF
BIT0:Frequency reference(Hz)
BIT1:Bus voltage
BIT2:S state BIT3:Y state
BIT4:AI1 voltage(V)
BIT5:AI2 voltage(V)
BIT6:Keyboard potentiometer voltage
BIT7:Count value
BIT8:Length value
BIT9:PLC stage
BIT10:Load speed
BIT11:PID reference
BIT12:Pulse reference (kHz)
Note
●
Once the AC drive is re-powered on after power down, the display includes the
selected parameters before power down by default.
●
If parameters to be monitored cannot be found in F7-03, F7-04 and F7-05, view
them in group U0.
If a parameter needs to be displayed
during running, set corresponding bit
to 1, and set F7-04 to hexadecimal
equivalent.
If a parameter needs to be displayed
during running, set corresponding bit
to 1, and set F7-05 to hexadecimal
equivalent.
View Parameters in Group U0
You can view parameter values by using operation panel, convenient for on-site commissioning,
or from the host computer by means of communication (address: 0x7000-0x7044).
U0-00 to U0-31 are the monitoring parameters in the running and stop status defined by F7-03
and F7-04.
■
Function Code
Parameter Name
U0-00
Running frequency
Display Range
0.00 to 500.00 Hz
U0-01
Frequency reference
0.00 to 500.0 Hz
U0-02
Bus voltage
0.0 to 3000.0 V
U0-03
Output voltage
0 to 1140 V
U0-04
Output current
0.00 to 655.35 A (AC drive power ≤ 55 kW)
0.0 to 6553.5 A (AC drive power > 55 kW)
U0-05
Output power
0 to 32767
U0-06
Output torque
-
200.0% to 200.0%
U0-07
S state
0 to 32767
U0-07: It displays state of S terminals. After the value is converted into a binary number, each
bit corresponds to a S.
"
1
"
indicates high level signal, and
"
0
"
indicates low level signal. The corr
-
esponding relationship between bits and S is described in the following table:
7
6
5
4
3
2
1
0
S8
S7
S6
S5
S4
S3
S2
S1
15
14
13
12
11
10
9
8
-
VS5 VS4 VS3 VS2 VS1
S10
S9