5.6.8 Overspeed Protection
Function Code
Parameter Name
Default
F9-67
Overspeed detection level
Setting Range
20.0%
0.0% to 50.0% (max. frequency)
F9-68
Overspeed detection time
1.0s
0.0s: Not detected
0.1 to 60.0s
These function parameters define motor overspeed detection that is effective only for vector
control with speed sensor.
When detected motor speed exceeds maximum frequency and the excess is larger than the value
of F9-67 for longer than time set in F9-68, the AC drive detects Err43 and acts as selected in the tens
position in F9-50.
If F9-68 is set to 0, motor overspeed detection is disabled.
5.6.9 Speed Error Protection
Function Code
Parameter Name
Default
F9-69
Detection level of speed error
Setting Range
20.0%
0.0% to 50.0% (max. frequency)
F9-70
Detection time of speed error
1.0s
0.0s to 60.0s
This function is effective only for vector control with speed sensor.
When detected motor speed is different from frequency reference and the difference is larger
than the value of F9-69 for longer than the time set in F9-70, the AC drive detects Err42 and acts as
selected in the units position in F9-50.
5.6.10 Undervoltage & Overvoltage Threshold and Overcurrent
Fast Prevention
Function Code
Parameter Name
Default
A5-06
Undervoltage threshold
Setting Range
350 V
210 to 420 V
A5-09
Overvoltage threshold
Model
dependent
200.0V
to
2500.0V
A5-04
Overcurrent fast prevention
1
0: Disabled
1: Enabled
When DC bus voltage exceeds the setting of A5-06/A5-09, the AC drive detects Err09/Err05–
Err07.
It is suggested that overcurrent fast prevention is disabled (A5-04 = 0) in hoist applications such
as crane.
5.6.11 Output Overcurrent Protection
This is to provide overcurrent protection for the AC drive.
If the drive's output current is equal to or smaller than the value set in F8-36 and the duration
exceeds the value set in F8-37, digital output terminal set for function 36 becomes on.
Function Code
Parameter Name
Default
F8-36
Output overcurrent threshold
Setting Range
200.0%
0.0% (no detection)
0.1% to 300.0% (rated motor current)
F8-37
Output overcurrent detection
delay
0.00s
0.01s to 600.00s