EC590
Function parameters description
-
39
-
-
40
-
EC590
Function parameters description
Master Command
Slave Response
ADDR
01H
CMD
06H
Parameter address high bits
20H
Parameter address low bits
00H
Data content high bits
00H
Data content low bits
02H
CRC high bits
03H
CRC low bits
CBH
ADDR
01H
CMD
06H
Parameter address high bits
20H
Parameter address low bits
00H
Data content high bits
00H
Data content low bits
02H
CRC high bits
03H
CRC low bits
CBH
5.2 Set Frequency Reference
The AC drive provides the following four methods to output the required frequency reference:
●
Main frequency reference
●
Auxiliary frequency reference
●
Main & auxiliary calculation
●
Command frequency reference setting channel
5.2.1 Set Main Frequency Reference
Main frequency reference has nine setting channels.
F0-03 selects a required channel to set the main frequency reference, described in the following
figure.
Function Code
Parameter Name
Default
F0-03
Main frequency
reference setting
channel selection
Setting Range
0
0: Digital setting (non-retentive at power down)
1: Digital setting (retentive at power down)
2: AI1
3: AI2
4: Keyboard potentiometer
5: Pulse reference
6: Multi-reference
7: Simple PLC
8: PID reference
9: Serial comms.
■
Digital Setting (Non-retentive at Power Down)
The initial value of frequency reference is F0-08(Preset frequency). You can modify frequency
reference by pressing
and
on the operating panel (or
using the UP/YWN function of input
terminals).When the AC drive is powered on again, frequency reference continues from the value of
F0-08.
■
Digital Setting (Retentive at Power Down)
The initial value of frequency reference is F0-08
(Preset frequency). You can change frequency
reference by pressing
and
on the operating panel (or using the UP/YWN function of input
terminals).When the AC drive is powered on again, frequency reference continues from where it last
reached.
Function Code
Parameter Name
Default
F0-08
Preset frequency
Setting Range
50.00 Hz
0.00 to max. frequency (F0-10)
F0-10
Max. Frequency
50.00 Hz
50.00 to 500.00 Hz
Note
F0-23 (Retentive selection of digital setting frequency upon stop) determines
whether to save frequency reference selection by pressing and or via the
up/down function when the AC drive stops. It is not the same as F0-03 = 0 or 1,
which determines whether to retain the setting on power-off.
Function Code
Parameter Name
Default
F0-23
Retentive selection of
digital setting frequency
upon stop
Setting Range
1
0: Not retentive
1: Retentive
F0-23 is valid only when frequency reference setting channel is digital setting.
●
F0-23 = 0: Non-retentiveThe AC drive resumes frequency reference to the value set in F0-08 at
stop. Frequency reference continues from the value of F0-08 at next power-on.
●
F0-23 = 1: retentive The AC drive retains the frequency reference that was last reached at stop.
Frequency reference continues from the retained value at next power-on.For example, F0-08 is set
to 40 Hz and you increase it to 45 Hz by pressing . If F0-23 = 0, The drive resumes frequency re-
ference to 40 Hz after stop. If F0-23 = 1, frequency reference remains at 45 Hz after stop.