background image

1 1

 -

1 2

 -

F a u l t s a n d s o l u t i o n s

EC590

 

O p e r a t i o n a n d d i s p l a y

EC590

 

7

.

1

 

LED operation panel

Note: The built-in keyboard has no panel potentiometer, but the pull-out keyboard includes it.

7

.

 Operation and display

7.2 Description of Keys on the LED operation panel

Key

Level

 

1

 

main

 

menu entry or exit.

Enter

 

the menu interface step by step; Set parameters 

Increment of data or function code.

Decrement of data or function code.

Function

In

 

the

 

shutdown

 

display

 

and

 

operation display interface,

the display parameters can be selected cyclically. When
modifying a parameter, you can select the modification 
bit of it.

In the keyboard operation mode, it is used to run the 
operation. 

Name

Programming

 

key

Confirm key

Incremental

 

key

Decrement key

Shift

 

key

Running

 

key

In the running state, press this key to stop; In the fault 
alarm state, press this key to reset; Its characteristics
are constrained by function F7-02.

Stop

/

Reset

Select function switching according to F7-01, which can be
defined as source, or fast direction switching.

Multiple

 

us

 

key

PRG
SET

RUN

RESET

MF.K

Err03

 

Overcurrent 

during 

deceleration

1: The output circuit is grounded 
or short circuited.
2: Motor auto-tuning is not 
performed.
3: The deceleration time is too 
short.
4: The input voltage is too low.
5: A sudden

load is added during 

deceleration.
6: The braking unit and braking 
resistor are not installed.
7: Subject to external inter-
ference.

1: Eliminate external faults.
2: Perform the motor autotuning.
3: Increase the deceleration time.
4: Adjust the voltage to the normal range.
5: Remove the added load.
6: Install the braking unit and braking 
resistor.
7: According to the historical fault 
records, if the current value at the time
of fault is far from reaching the over-
current point value, it is necessary to 
find the interference suorce.

Err04

Overcurrent 
at constant 

speed

1: The output circuit is grounded 
or short circuited.
2: Motor auto-tuning is not 
performed.
3: The input voltage is too low.
4: A sudden load is added during 
operation.
5: The AC drive model is of too 
small power class.
6: Subject to external inter-
ference.

1: Eliminate external faults. 
2: Perform the motor autotuning. 
3: Adjust the voltage to the normal range. 
4: Remove the added load. 
5: Select an AC drive of higher power 
class.
6: According to the historical fault 
records, if the current value at the time
of fault is far from reaching the over-
current point value, it is necessary to 
find the interference suorce.

Err05

Overvoltage 

during 

acceleration

1: The input voltage is too high.
2: An external force drives the 
motor during acceleration.
3: The acceleration time is too 
short.
4: The braking unit and braking 
resistor are not installed.
5: Subject to external inter-
ference.

1: Adjust the voltage to normal range.
2: Remove the external force or install a 
braking resistor.
3: Increase the acceleration time.
4: Install the braking unit and braking 
resistor.
5: According to the historical fault 
records, if the current value at the time
of fault is far from reaching the over-
current point value, it is necessary to 
find the interference suorce.

8.Faults and solutions

 

Display

Err02

Fault 

name

Overcurrent 

during 

acceleration

Possible causes

1: The output circuit is grounded 
or short circuited.
2: Motor auto-tuning is not 
performed.
3: The acceleration time is too 
short.
4: Manual torque boost or V/F 
curve is not appropriate.
5: The input voltage is too low.
6: The startup operation is 
performed on the rotating motor.
7: A sudden load is added during 
acceleration.
8: The AC drive model is of too 
small power class.
9: Subject to external inter-
ference.

Solutions

1: Eliminate external faults.
2: Perform the motor auto

-

tuning.

3: Increase the acceleration time.
4: Adjust the manual torque boost or V/F 
curve.
5: Adjust the voltage to the normal range.
6: Select rotational speed tracking 
restart or start the motor after it stops.
7: Remove the added load.
8: Select an AC drive of higher power 
class.
9: According to the historical fault 
records, if the current value at the time
of fault is far from reaching the over-
current point value, it is necessary to 
find the interference suorce.

MF.K

RESET

PRG

SET

RUN

Содержание EC590 Series

Страница 1: ...0 in 2022 Copyright subject to change without notice Professional AC Drive Manufacturer ZHEJIANG EACN ELECTRONIC TECHNOLOGY CO LTD Address No 1 Jinhe Road Qinshan Street Haiyan County Jiaxing City Zh...

Страница 2: ...s 9 5 F4 Input Terminals 9 6 F5 Output Terminals 9 7 F6 Start stop control 9 8 F7 Operating panel and display 9 9 F8 Auxiliary Functions 9 10 F9 Fault and Protection 9 11 FA PID Function 9 12 FB Fixed...

Страница 3: ...e read carefully If you have any questions please contact with the agents of our company and our technicians are ready to serve you The instructions are subject to change without notice You can contac...

Страница 4: ...range of 0 0 6500 0s DC braking JOG control DC braking frequency 0 00 Hz to maximum frequency Braking time 0 0 100 0s Braking action current value 0 0 150 0 Simple PIC Multiple preset speeds JOG frequ...

Страница 5: ...It helps to avoid frequent overcurrent faults of the AC drive Timing control Time range 0 0 6500 0 minutes Individua lized functions Multiple communication protocols It supports Modbus Item Specifica...

Страница 6: ...171 160 130 127 4 5 1 5Kw 2 2Kw 4 0Kw 7 5Kw 18 5Kw 15Kw 126 146 170 115 131 151 320 186 256 175 243 305 158 174 198 155 171 195 4 5 6 6 30Kw 5 5Kw 11Kw 22Kw A Structure 45Kw 75Kw 180 250 120 170 489 6...

Страница 7: ...C 0V 10V 2 Impedance 22k 1 Input range DC 0V 10V 4mA 20mA decided by selection of F4 40 2 Impedance 22k voltage input 500 current input 10V GND 24V COM PLC AI1 GND AI2 GND Name External 10V power supp...

Страница 8: ...sudden load is added during operation 5 The AC drive model is of too small power class 6 Subject to external inter ference 1 Eliminate external faults 2 Perform the motor autotuning 3 Adjust the volta...

Страница 9: ...oard is faulty 4 The module is faulty 1 Eliminate external faults 2 Check whether the motor three phase winding is normal 3 Seek technical support 4 Seek technical support 13 14 Err14 Module overheat...

Страница 10: ...ameter protection password is set In the function parameter mode and user change parameter mode the parameter menu can only be entered after correctly entering the password Set FP 00 to 0 to cancel th...

Страница 11: ...anel keypad display 0 No function 1 Digital setting 2 AI1 3 AI2 4 Keyboard potentiometer 5 Pulse reference S5 6 Multi reference 7 Simple PLC 8 PID reference 9 Serial communication Tens terminal contro...

Страница 12: ...V F complete separation 11 V F half separation Default 0 Parameter Name F3 02 Cut off frequency of torque boost 0 00 Hz to the maximum frequency 50 00Hz F3 03 F3 04 F3 05 F3 06 F3 07 F3 08 Multi poin...

Страница 13: ...control switchover 47 Emergency stop 48 External STOP terminal 2 49 Deceleration DC injection braking 50 Clear the current running time 51 Two wire Three wire mode switchover 52 Reverse frequency forb...

Страница 14: ...specified count value reached 10 Length arrives 11 PLC cycle completed 0 2 F5 06 F5 07 0 Operationg frequency 1 Set frequency 2 Output current 3 Output torque torque absolute value 4 Output power 5 O...

Страница 15: ...l Change Function Code Setting Range Default Parameter Name 0 Speed tracking method 0 Start with stop frequency 1 Start from zero speed 2 Start from maximum frequency 0 F6 02 Speed tracking speed 1 10...

Страница 16: ...eference Hz BIT0 1 Bus voltage BIT0 2 S state BIT0 3 YO state BIT0 4 AI1 voltage V BIT0 5 AI2 voltage V BITO 6 Keyboard potentiometer voltage BIT0 7 Count value BITO 8 Length value BIT0 9 PLC stage BI...

Страница 17: ...d 0 00Hz F8 25 Switch over frequency of acceleration time 1 and acceleration time 2 0 00Hz to the maximum frequency F8 26 Switch over frequency of deceleration time 1 and deceleration time 2 0 00Hz to...

Страница 18: ...upon 3rd latest fault Current upon 3rd latest fault 3rd latest fault type F9 19 F9 20 Bus voltage upon 3rd latest fault S state upon 3rd latest fault Y state upon 3rd latest fault F9 21 Power on time...

Страница 19: ...reached Err29 0 Coast to stop 1 Stop according to the stop mode 2 Continue to run BIT3 Load lost Err30 0 Coast to stop 1 Deceleration to stop 2 Continue to run at 7 of rated motor frequency and restor...

Страница 20: ...d 0 00 to 60 00s 0 AI1 1 AI2 2 Keyboard potentiometer 3 AI1 AI2 4 Pulse reference S5 5 Communication reference 6 AI1 AI2 7 Max AI1 AI2 8 Min AI1 AI2 0 0 FA 03 PID operation direction 0 Forward 1 Rever...

Страница 21: ...ence 4 FC 29 FC 28 Running time of simple PLC reference 5 0 0s h to 6553 5s h Acceleration Deceleration time of simple PLC reference 4 0 to 3 Running time of simple PLC reference 6 FC 30 0 0s h to 655...

Страница 22: ...mmunication detection time FE 00 User defined parameter 0 U3 17 FE 01 User defined parameter 1 F0 00 F0 00 FC 47 Acceleration Deceleration time of simple PLC reference 14 0 to 3 Running time of simple...

Страница 23: ...ter 27 F0 00 FE 28 User defined parameter 28 F0 00 FE 29 User defined parameter 29 F0 00 F0 00 to FP xx A0 00 to Ax xx U0 00 to U0 xx U3 00 to U3 xx FP Parameter Management Change Function Code Settin...

Страница 24: ...2 10 A2 27 A2 28 Rotor resistance Leakage inductive reactance Mutual inductive reactance No load current Encoder pulses per revolution Encoder type 0 001 to 65 535 AC drive power 55 kW 0 0001 to 6 553...

Страница 25: ...0 DPWM switchover frequency upper limit 5 00 Hz to the maximum frequency 0 Asynchronous modulation 1 Synchronous modulation A5 02 Dead zone compensation mode selection 0 Disabled 1 Enabled compensatio...

Страница 26: ...ump range A7 User Programmable Card Change Function Code Setting Range Default Parameter Name 0 Disabled 1 Enabled A7 01 Control board output terminal control mode selection 0 0 AC drive control 1 Use...

Страница 27: ...tory corrected Factory corrected Factory corrected Factory corrected Factory corrected Factory corrected Factory corrected Factory corrected U Minimum Unit UO Monitoring Parameters Function Code Param...

Страница 28: ...de parameters some function codes cannot be changed only for manufacturers to use or monitor function code parameter address marking rules The rules are represented by the function code group number a...

Страница 29: ...BIT1 Y2 output control BIT2 RELAY1 output control BIT3 RELAY2 output control BIT4 Y4R output control BIT5 VY1 BIT6 VY2 BIT7 VY3 BIT8 VY4 BIT9 VY5 2001 Digital output terminal control write only Comman...

Страница 30: ...4 port is constrained by the functional parameter F5 00 and can be used as a high speed pulse output channel with a maximum output frequency of 50KHz when used as an open collector output Same specifi...

Отзывы: