background image

 

 

European Safety Systems Ltd.

  Impress House, Mansell Road, Acton, London W3 7QH 

 

 

 

 

 

[email protected]  Tel: +44 (0)208 743 8880 

Document D150-00-701-IS   Issue 6   11-08-2022 

 

 

Sheet 2 of 2 

 

 

 

www.e2s.com  Fax +44 (0)208 740 4200 

The equipment is certified for use in ambient 
temperatures in the range -40

o

C to +55

o

C and shall 

not be used outside this range. 
 

4) 

Installation Requirements 

 Installation of this equipment shall only be carried 
out  by  suitably  trained  personnel  in  accordance 
with the applicable code of practice e.g. 
 
IEC 60079-14/EN 60079-14. 

 

Repair of this equipment shall only be carried out 
by the manufacturer or in accordance with the 
applicable code of practice e.g. IEC 60079-19/EN 
60079-19. 

 

The  certification  of  this  equipment  relies  on  the 
following materials used in its construction: 
 
Enclosure:

 

Aluminium  Pressure  Die  Cast  Body 

LM6 
 
Through enclosure mechanism: Plastic Nylon Zytel 
Injection Moulded 
 
Sealing  of  enclosure  and  mechanism:  O-ring 
Acrylonitrile-Butadiene Rubber  
 
If the equipment is likely to come into contact with 
aggressive substances,  then it is the  responsibility 
of the user to take suitable precautions that prevent 
it from being adversely affected, thus ensuring that 
the type of protection is not compromised. 
 
“Aggressive  substances”  -  e.g.  acidic  liquids  or 
gases that may attack metals, or solvents that may 
affect polymeric materials. 
 
“Suitable precautions” - e.g. regular checks as part 
of  routine  inspections  or  establishing  from  the 
material’s  data  sheet  that  it  is  resistant  to  specific 
chemicals. 
 
Refer  to  certificates  SIRA  09ATEX2287X,  IECEx 
SIR  09.0122X  and  CSAE  21UKEX2555X  for 
special conditions of safe use. 
 

5) 

Call Point Location and Mounting 

The location of the call point should enable ease of 
access  for  operation  and  testing.  The  unit  should 
be  mounted  using  the  4  off  fixing  holes  which  will 
accept up to M4 sized fixings. 
 

When installing in Zone 0 applications, ensure that 
the equipment enclosure is protected from impact. 
 

 

 
View of base unit showing fixing centres. 
 
 
To  gain  access  to  the  mounting  holes  in  the  base 
the front cover must be removed.  
 
 
This  is  achieved  by  removing  the  4  off  M4  cap 
head bolts holding on the cover. 
 

 

 
Once the screws are removed the cover  will hang 
down  out  of  the  way  to  gain  access  to  the  Ex  e 
terminal  block,  the  internal  earth  terminal  and 
mounting hole recesses. 

6) 

Earthing 

The  unit  has  both  internal  and  external  earth 
terminals. 
It  is  recommended  that  a  cable  crimp  lug  is  used 
on the earth wires. 
The  internal  earth  wire  is  placed  under  a  earth 
clamp  which  will  stop  the  cable  twisting.  This  is 
secured by an M4 screw and spring washer. 
The  external  earth  lug  should  be  located  between 
the two M5 washers provided and securely locked 
down with the M5 spring washer and two locknuts. 
 

 

Internal Earth 
terminal 

 

 

External 

 

 

               Earth Stud 

 

Terminal block 

 

7) 

Cable connections 

There  are  3  off  cable  entries  for  M20x1.5  Ex  t 
approved cable glands or stopping plugs. 
 
Cable glands or stopping plugs must be rated IP66. 
 
The unit can be wired in a number of different ways 
depending  whether  normally  open  or  normally 
closed contacts are required. 
 
The  equipment  needs  to  be  installed  with  ATEX 
and/or  IECEx  certified  Zener  Barriers  or  Galvanic 
Isolators. 
 
For wiring schematic refer to drawing D150-06-001 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание IS-CP4A-PT

Страница 1: ...P4A PT is a tool reset manual call point which is certified intrinsically safe to the European and International Gas and Dust standards The unit meets the requirements of the ATEX directive 2014 34 EU...

Страница 2: ...certificates SIRA 09ATEX2287X IECEx SIR 09 0122X and CSAE 21UKEX2555X for special conditions of safe use 5 Call Point Location and Mounting The location of the call point should enable ease of access...

Страница 3: ...VE MATTER THEREIN IS COMMUNICATED IN CONFIDENCE AND IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY SYSTEMS LTD NEITHER THE WHOLE OR ANY EXTRACT MAY BE DISCLOSED LOANED COPIED OR USED FOR DRAWING TO BS88...

Страница 4: ...a 55 C II 2D Ex tb IIIC T60 C Db 40 C Ta 55 C IP6X Dust Protection to EN60079 0 EN60079 31 IS CP4B II 1G Ex ia IIC T4 Ga 40 C Ta 55 C BEx CP5B II 2D Ex tb IIIC T70 C Db 40 C Ta 50 C IP6X Dust Protecti...

Страница 5: ...and Place of Issue London 23 12 2020 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the ma...

Страница 6: ...Dust Protection to EN60079 0 EN60079 31 IS CP4B II 1G Ex ia IIC T4 Ga 40 C Ta 55 C BEx CP5B II 2D Ex tb IIIC T70 C Db 40 C Ta 50 C IP6X Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC...

Страница 7: ...and Place of Issue London 04 02 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the...

Отзывы: