Testing unit operation 

The tool  reset unit can be  tested without the need 
to replace any element.  
 
To test, lift the cover lift flap to reveal the tool reset 
button. The button should be pressed into the body 
to  activate  the  unit  and  place  it  into  the  operated 
condition. 
 

 

 
 
The  call  point  switch  will  now  change  over  it’s 
contacts to operate the alarm. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Once testing is complete the unit needs to be reset 
from the operated condition.  
 
Using the special reset tool provided the tool reset 
button is rotated anticlockwise by an angle of 55º, 
see  guide  alignment  marks  on  button  and  cover, 
shown below (1). The tool reset button should pop 
back up to its original position. 
Ensure  that  the  tool  reset  button  has  also  twisted 
back  clockwise  by  55º  to  its  original  position  see 
guide marks on button and cover, shown below (2). 
The unit is now reset. 
 

 

 
 

1. On operated unit 

         2. Button should pop 

Twist tool reset button           up and twist back to 
Anticlockwise 55º 

         original position 

with special key to reset 

 

          

 
 

 
Note: use 
alignment marks 
circled to indicate 
the tool reset 
buttons status 
/position.  
 
Unit currently 
shown as ‘standby 
condition’ 
 

Resetting an operated unit is the same as resetting 
a tested unit. 

 

IS-CP4A-PT 

Manual Call Point – Tool Reset 

For use in Flammable Gas and 
Combustible Dust Atmospheres 
 

 

1) 

Introduction 

The  IS-CP4A-PT  is  a  tool  reset  manual  call  point 
which is  certified intrinsically safe to the European 
and International Gas and Dust standards. The unit 
meets  the  requirements  of  the  ATEX  directive 
2014/34/EU and IECEx scheme. 
 
The  call  point  can  be  used  in  hazardous  areas 
where  potentially  flammable  gas  and  dust 
atmospheres may be present. 
 
The IS-CP4A-PT has no monitoring resistors.  The 
units  are  Group  II,  EPL  (equipment  protection 
level)  Ga.  The  equipment  is  certified  ‘Ex  ia  IIC  T6 
Ga’ and as such may be used in Zones 0, 1 and 2 
with flammable gases and vapours with gas groups 
IIA, IIB &  IIC and temperature classes T1, T2, T3, 
T4, T5 and T6. 
 
These  units  are  also  Group  III,  EPL  Db.  The 
equipment  is  certified  ‘Ex  t  IIIC  T60ºC  Db’  and  as 
such  may  be  used  in  Zones  21  and  22  for 
combustible dusts groups IIIA, IIIB & IIIC. 
 
The  equipment  needs  to  be  installed  with  ATEX 
and/or  IECEx  certified  Zener  Barriers  or  Galvanic 
Isolators 

2) 

Marking 

All  units  have  a  rating  label,  which  carries  the 
following important information:- 
 
Unit Type No.: 
IS-CP4A-PT Manual Call Point 
 
Code: 
Ex ia IIC T6 Ga 
Ex tb IIIC T60 ºC Db 
IP66 
–40ºC <= Ta <= +55ºC 
 
Input Voltage: Dust Protection Ex t 
AC voltage 250V Max Current 5.0A Max 
DC voltage 56V Max Current 1.0A Max 
 
Input Voltage: Gas Protection Ex ia 
Ui=30V Ii=500mA Pi=1.1W Ci=0 Li-0 
 
Certificate No.: 
SIRA 09ATEX2287X 
IECEx SIR 09.0122X 
CSAE 21UKEX2555X 
 
Epsilon x:                           II 1G2D 
 
 
CE Marking 
Notified  

  

2813 

Body No.               
 
UKCA Marking 
Notified Body No.

 

0518 

 
 
Year/Serial No. i.e. 10/1CP4APT000001   
 
WARNING - DO NOT OPEN WHEN AN 
EXPLOSIVE ATMOSPHERE MAY BE PRESENT 

 
3) 

Type Approval Standards 

The  beacon  has  an  EC  Type  examination 
certificate issued by SIRA and have been approved 
to the following standards:- 
 
EN IEC 60079-0:2018 / IEC 60079-0:2017 
EN 60079-11:2012 / IEC 60079-11:2011 
IEC 60079-26:2014 
 
EN 60079-31:2014 / IEC 60079-31:2013

 

Содержание IS-CP4A-PT

Страница 1: ...P4A PT is a tool reset manual call point which is certified intrinsically safe to the European and International Gas and Dust standards The unit meets the requirements of the ATEX directive 2014 34 EU...

Страница 2: ...certificates SIRA 09ATEX2287X IECEx SIR 09 0122X and CSAE 21UKEX2555X for special conditions of safe use 5 Call Point Location and Mounting The location of the call point should enable ease of access...

Страница 3: ...VE MATTER THEREIN IS COMMUNICATED IN CONFIDENCE AND IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY SYSTEMS LTD NEITHER THE WHOLE OR ANY EXTRACT MAY BE DISCLOSED LOANED COPIED OR USED FOR DRAWING TO BS88...

Страница 4: ...a 55 C II 2D Ex tb IIIC T60 C Db 40 C Ta 55 C IP6X Dust Protection to EN60079 0 EN60079 31 IS CP4B II 1G Ex ia IIC T4 Ga 40 C Ta 55 C BEx CP5B II 2D Ex tb IIIC T70 C Db 40 C Ta 50 C IP6X Dust Protecti...

Страница 5: ...and Place of Issue London 23 12 2020 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the ma...

Страница 6: ...Dust Protection to EN60079 0 EN60079 31 IS CP4B II 1G Ex ia IIC T4 Ga 40 C Ta 55 C BEx CP5B II 2D Ex tb IIIC T70 C Db 40 C Ta 50 C IP6X Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC...

Страница 7: ...and Place of Issue London 04 02 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the...

Отзывы: