background image

 

 

European Safety Systems Ltd.

  Impress House, Mansell Road, Acton, London W3 7QH 

 

 

 

 

 

 

 

www.e2s.com  Tel: +44 (0)208 743 8880 

Document D154-00-155-IS   Issue 8  12-09-2022 

 

 

Sheet 2 of 3 

 

 

 

 

 

 
 
 
 
 
 
 

 

 

 

 

 
 
Once  the  screws  are  removed  the  cover  will  hang 
down  out  of  the  way  to  gain  access  to  the  Ex  e 
terminal  block,  the  internal  earth  terminal  and 
mounting hole recesses. 
 

6) 

Earthing 

The unit has an internal earth terminal. 
It  is  recommended  that  a  cable  crimp  lug  is  used 
on the earth wires. 
The  internal  earth  wire  is  placed  under  an  earth 
clamp  which  will  stop  the  cable  twisting.  This  is 
secured by an M4 screw and spring washer. 
 
 

 

 
 
 
 

 
 

 

 
Internal Earth 

Ex e terminal block 

terminal 

 

 

 

7) 

Cable connections 

There  are  3  off  cable  entries  for  M20x1.5  Ex  e 
approved  cable  glands  or  stopping  plugs  with  a 
minimum ingress protection of IP66 
 
The unit can be wired in a number of different ways 
depending on the device combination selected. 
 
EOL (End of line) device:  
resistor – ExxxR / diode – ED1 / zener – ExxxZ  
Series (In line) device: 
resistor  –  SxxxR  /  diode  –  SD1  /  zener  –  SxxxZ  / 
LED  
Microswitch 1 = M/S 1 
Microswitch 2 = M/S 2 
 
The unit can be wired with a maximum of 2 module 
devices – refer to wiring schematic D154-06-051 
 
When  wiring  to  Increased  Safety  terminal 
enclosures,  you are only permitted  to  connect  one 
wire  into  each  way  on  the  terminal  block  unless  a 
pair of wires are crimped into a suitable ferrule. For 
the six-way terminal block wire sizes allowable are 
0.5mm²  to  4.0mm².  For  the  8-way  DIN  rail  wire 
sizes allowable are 0.5mm² to 2.5mm² 
 
Leads connected to the terminals shall be insulated 
for the appropriate voltage and this insulation shall 
extend  to  within  1mm  of  the  metal  of  the  terminal 
throat.  They  shall  only  be  installed  and  wired  with 
cable in an ambient temperature of -10°C to +80°C 
 
All  terminal  screws,  used  or  unused,  shall  be 
tightened down to between 0.5 Nm and 0.7 Nm. 
 

Voltage 
option 

Max 
Voltage  

Min resistor value 
allowable in 
module 
Type C unit (1.5W) 

6 V dc 

6 V dc 

27 ohms 

12V dc 

12 V dc 

110 ohms 

24V dc 

24 V dc 

430 ohms 

48V dc 

48 V dc 

1K8 ohms 

Table 1 

 
 
 
 
 
 
 
 
 

7.1)     Current Limitations 

The  maximum  allowable  current  is  determined  as 
the smallest value from the following scenarios:

 

 

1. 

When  both  module  resistor  values  are  the 
same  as  or  above  the  minimum  range  of 
values  shown  in  table  1,  the  current  is  not 
further limited. 
However,  when  either  resistor  value  is 

lower

 

than those shown in table 1, the current must 
be limited to the values given in table 2. 
 

Voltage 
option 

Max 
Voltage  

Max current when 
resistor values 
lower than 
minimum 

6 V dc 

6 V dc 

250mA 

12V dc 

12 V dc 

125mA 

24V dc 

24 V dc 

62mA 

48V dc 

48 V dc 

31mA 

Table 2 

 

For example, if a 24V DC unit is fitted with a 
series  resistor  of  270  ohms,  the  maximum 
current of the unit would be reduced to 62mA 
since the resistance is less than the minimum 
430 ohms allowable at this voltage. 
 
E2S  recommends  a  minimum  resistor  value 
of  100  ohms  for  a  Series  device  and  180 
ohms for an EOL device fitted to a 24V unit. 
 

2. 

If  a  diode  module  is  pre-fitted  as  either  an 
EOL  or  Series  Device,  the  following  current 
limitation applies: 
 

Unit Voltage 

Max. Diode Current 

48V DC 

0.75A 

6, 12 & 24V DC 

2.0A  

 
3. 

If a Zener diode module is pre-fitted as either 
EOL  or  Series  device,  the  following  current 
limitation applies: 

 

Zener 
Voltage 

Max. Input 
Voltage 

Max. Current 

3.3V 

56V DC 

230mA 

4.7V 

162mA 

5.1V 

149mA 

5.6V 

136mA 

6.2V 

122mA 

6.8V 

112mA 

10V 

76mA 

12V 

63mA 

4. 

Units with LED code ‘C’ 

 

GNExCP6C-PBXXXXXXXXX

C

-XX-ExxxR-SxxxR  

 

Maximum  current  is

  reduced  to  20mA.

  In 

this  case,  the  current-limiting  resistor  for  the 
LED  is  not  present,  so  that  to  safely  power 
the  LED  the  maximum  current  must  be 
limited. 

 

For  units  with  LED  code  ‘L’,  the  current  is 
limited  by  the  LED  current-limiting  resistor. 
See value of this resistor in table below.  

 

GNExCP6C-PBXXXXXXXXX

L

-XX-ExxxR-SxxxR  

 

LED Resistor 

Max. Input Voltage 

3K3 (3300 ohms) 

56V DC 

1K5 (1500 ohms) 

28V DC 

 

8) 

Testing unit operation 

The  push  button  unit  can  be  tested  without  the 
need to replace any element. 
 
To  test,  lift  the  cover  lift  flap  to  reveal  the  push 
button. The button should be pressed into the body 
to  activate  the  unit  and  place  it  into  the  operated 
condition. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The  call  point  switch  will  now  change  over  its 
contacts to operate the alarm. 
 
Once testing is complete the unit needs to be reset 
from the operated condition. 
 
 
 
 

Содержание GNExCP6C-PB

Страница 1: ...by SIRA and have been approved to the following standards EN60079 0 2018 IEC60079 0 2017 EN60079 1 2014 IEC60079 1 2014 EN60079 7 2015 IEC60079 7 2017 EN60079 18 2015 IEC60079 18 2014 EN60079 31 2014...

Страница 2: ...ent Limitations The maximum allowable current is determined as the smallest value from the following scenarios 1 When both module resistor values are the same as or above the minimum range of values s...

Страница 3: ...EC EN61508 which has been assessed and is considered suitable for use in low demand safety function Random Hardware Failures and Systematic Failures route 2H As an unvoted item i e hardware fault tole...

Страница 4: ...DED CONFIG 8 AND 12 ADDED LED ONLY CONFIG 13 REMOVED CONFIGS RE NUMBERED 1 TO 24 4 warning signals Circuit shown in Unoperated condition Unoperated condition Glass Intact Standby Condition Terminals 2...

Страница 5: ...cuit shown in Unoperated condition Unoperated condition Glass Intact Standby Condition Terminals 1 2 M S 1 and 4 5 M S 2 open Terminals 1 3 M S 1 and 4 6 M S 2 closed Operated condition Glass Broken B...

Страница 6: ...ng signals Circuit shown in Unoperated condition Unoperated condition Glass Intact Standby Condition Terminals 2 3 4 5 open Terminals 2 3 6 closed Operated condition Glass Broken Button pushed in Term...

Страница 7: ...he LED current limiting resistor RL1 using LED option C In all other cases RL1 is included Circuit shown in Unoperated condition Unoperated condition Glass Intact Standby Condition Terminals 2 3 M S 1...

Страница 8: ...S 1 M S 2 open Terminals 2 3 6 M S 1 M S 2 closed Operated condition Glass Broken Button pushed in Terminals 2 3 4 5 M S 1 M S 2 closed Terminals 2 3 6 M S 1 M S 2 open Circuit shown in Unoperated co...

Страница 9: ...rated condition Glass Broken Button pushed in Terminals 3 4 5 6 M S 1 M S 2 closed Terminals 3 4 7 M S 1 M S 2 open Circuit shown in Unoperated condition Unoperated condition Glass Intact Standby Cond...

Страница 10: ...surance Notification Conformity to EU type based on quality assurance of the production process Module D Sira Certification Service Notified Body No 2813 CSA Group Netherlands B V Utrechtseweg 310 681...

Страница 11: ...and electronic equipment including amendment by Directive 2015 863 EU Regulation EC 1907 2006 Registration Evaluation Authorisation and Restriction of Chemicals REACH The product and all the componen...

Страница 12: ...t GNExCP6A GNExCP6B GNExCP6C GNExCP6D GNExCP6E II 2G Ex db eb IIC T6 Gb 40 C Ta 70 C II 2D Ex tb IIIC T75 C Db 40 C Ta 70 C or II 2G Ex db eb mb IIC T4 Gb 40 C Ta 50 C II 2D Ex tb IIIC T80 C Db 40 C T...

Страница 13: ...ity Other Standards and Regulations EN 60529 1992 A2 2013 Degrees of protection provided by enclosures IP code enclosure rated IP66 On behalf of European Safety Systems Ltd I declare that on the date...

Отзывы: