8.3.5 Control of circuit protectors
Register 47301 – 47316 for channel 1-16, writable, functional codes 6 and 16.
It is possible to access the circuit protectors from the superordinate control unit. Each channel of each
electronic circuit protector can be switched on or off or reset. Switch on or off is only possible if correspond-
ing PLCLock Bit is set to false.
value range: 0–65535
data length: 1 word
Word
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
load output
(ON/OFF)
0/1*
reset
0/1*
overload
0/1*
reserve
0/1*
reserve
0/1*
reserve
0/1*
reserve
0/1*
reserve
0/1*
Word
bit 15
bit 14
bit 13
bit 12
bit 11
bit 10
bit 9
bit 8
description
32768
16384
8192
4096
2048
1024
512
256
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
reserve
0/1*
reserve
0/1*
reserve
0/1*
reserve
0/1*
reserve
0/1*
reserve
0/1*
reserve
0/1*
reserve
0/1*
* status not set = 0 / status set = 1
fig. 22: Controlling the circuit protectors
8.3.6 System commands EM12D
Register 46001, writable, functional code 6.
Depending to transmitted value one of following functions will be executed.
8.3.6.1 Reset to factory settings
Set Value 130 at Register load default Parameter at supply modul.
8.3.6.2 Reset statistical information
Set Value 250 at Register reset all Statisticinformation at all channels. It is equally possible to reset these
pieces of information channel-wise. This is described in the chapter of the action commands.