18
Modbus
register
functional
code
write/read
multiplication
factor
description
40119
3
read
100
Ø load current F1
40219
3
read
100
Ø load current F2
40319
3
read
100
Ø load current F3
•
•
•
41619
3
read
100
Ø load current F16
40120
3
read
100
max. load current F1
40220
3
read
100
max. load current F2
40320
3
read
100
max. load current F3
•
•
•
41620
3
read
100
max. load current F16
40121
3
read
100
min. load current F1
40221
3
read
100
min. load current F2
40321
3
read
100
min. load current F3
•
•
•
41621
3
read
100
min. load current F16
40122
3
read
device type F1
40222
3
read
device type F2
40322
3
read
device type F3
•
•
•
41622
3
read
device type F16
40123
3
read
hardware version F1
40223
3
read
hardware version F2
40323
3
read
hardware version F3
•
•
•
41623
3
read
hardware version F16
40124
3
read
softwareversion major.x.x F1
40224
3
read
software version major.x.x F2
40324
3
read
software version major.x.x F3
•
•
•
41624
3
read
software version major.x.x F16
Содержание EM12D-TMB Series
Страница 1: ...Instruction manual Controller EM12D TMB ...
Страница 37: ...37 ...