27
8.3.14 Application Specific Tag EM12D
Register 46014 – 46029 for channel 1-16, writable, functional codes 3 and 16.
A customer-specific text can be entered here. The text can hold up to 32 characters. One register holds two
characters.
value range: text
data length: 16 word
8.3.15 Current rating REX12D
Register 4(01..16)01 for channel 1-16, readable, writable, functional codes 3 and 6.
The parameter returns the current rating of the channel in Amp, depending on the device type. This value is
both readable and writable.
value range: 1-10 (integer)
default value: 1
data length: 1 word
8.3.16 Limit value load current REX12D
Register 4(01..16)02 for channel 1-16, readable, writable, functional codes 3 and 6.
The parameter determines at how many percent of the rated current the channel will signal "limit value
exceeded". This parameter is readable/writable.
value range: 50 % - 100 % (whole numbers)
default value: 80 %
data length: 1 word