PULL DOWN MENUS
4-3
September 1994
Part No. 001-2008-300
Figure 4-6 ALARM CONFIGURATION
Use the arrow keys to move down the list. Use
the Space bar to toggle through the parameters: Dis-
abled, Active Low, Active High, for each alarm.
INPUT ALARMS
There are eight input alarms that can be activated
by external devices (see Section 6.8). These inputs
can be disabled, energized or de-energized.
If the input is disabled, the input alarm line is
inactive. When energized and current flow is
detected, the alarm is activated. When de-energized
and no current flow is detected, the alarm is activated.
Figure 4-7 INPUT ALARMS
OUTPUT TYPE SELECTION
Selects the operation of the Output Alarm. The
available types are:
Active Open - An active alarm opens (no contact)
the output lines.
Active Closed - An active alarm closes (contact)
the output lines.
Figure 4-8 OUTPUT ALARMS
ALARM DESCRIPTION
This is a text string (up to 15 characters) to
describe the alarm. This text string is sent via Morse
code if the alarm input is programmed and an output is
selected in the cross reference menu (see Figure 4-9).
ALARM TRANSMIT RATE
Sets the time interval for transmitting the alarm
message in Morse code (1-255 min, 0=disabled). If
more than one alarm is active, this is the inter-alarm
time.
CROSS REFERENCE
The cross reference screen selects the output
alarm that is activated by each input alarm. There are
up to 48 alarms (0-47), 8 external input alarms and 40
internal alarms (see Table 1-2). There are eight output
alarms. An alarm condition on any input can cause an
output alarm. This screen configures which input
alarm activates an output alarm.
NOTE: More than one alarm condition can have the
same output alarm (see Figure 4-9).
Select Which Alarms To Edit
Input Alarms
Output Alarms
Cross Reference
Input Alarm Configuration
Input Type Selection
Description
Spacebar
Door 1 open
Door 2 open
Alarm 1 Input Type: Energized
Alarm 2 Input Type: De-Energized
Alarm 3 Input Type: Analog
Alarm 4 Input Type: Analog
Fuel Tank 1/2
Fuel Tank 1/4
High Limit Voltage (Input3): 2.5 Volts
Low Limit Voltage (Input3): 1.6 Volts
High Limit Voltage (Input4): 1.5 Volts
Low Limit Voltage (Input4): 0 Volts
Description
Spacebar
Output Alarm Configuration
Output Type Selection
Tx ID
Alarm 1 Output Type: Active Open
Alarm 2 Output Type: Active Open
Alarm 3 Output Type: Active Open
Alarm Tx Rate:
0
Press F2 to Accept
DOOR OPEN
FUEL 1/2
FUEL 1/4
RF HALF POWER
Alarm 4 Output Type: Active Closed
15
120
120
0