User Manual HTS801
Humidity and Temperature Sensor for High Humidity and Chemically Polluted Conditions | 37
5.6
Integrated Power Supply 100 - 240 V AC (Option AM3)
WARNING
If the stainless steel enclosure is equipped with an alarm module (option AM2) or an integrated power supply
100 - 240 V AC (option AM3) and installation is not carried out correctly, there is the danger of a touch
voltage.
The HTS801’s stainless steel enclosure must therefore be grounded during operation.
Option E4
Power
analogue output
1
2
3
4
5
GND
GND Output
OUT 2
V+
OUT 1
Option E5
Modbus RTU
M16x1.5
Option E6
Digital RS485
Interface
Power
analogue output
Option E12
Modbus RTU
power
analogue output
Option AM3
1
2
3
4
5
GND
GND Output
OUT 2
V+
OUT 1
neutral wire
(N)
grounding
(PE)
phase
(L1)
Power supply 100 - 240 V AC
for stainless steel enclosure
2
1
4
3
5
RS485 B
(=D-)
GND RS485
(shielded)
RS485 A
(=D+)
n.c.
n.c.
2
1
4
3
5
RS485 B
(=D-)
GND RS485
(shielded)
RS485 A
(=D+)
n.c.
n.c.
2
1
4
3
5
RS485 B
(=D-)
GND RS485
(shielded)
RS485 A
(=D+)
n.c.
Modbus RTU
n.c.
Standard
2x M16x1.5
Option J4
V+
GND
GND
OUT 1
OUT 2
GND RS485
RS485 A (=D+)
RS485 B (=D-)
1
2
3
4
5
6
7
8
6
4
5
3
1
2
NO
NC
C
Standard operation mode
REL 1
NO
NC
C
REL 2
RELA
Y 2
RELA
Y 1
Option AM2
NC
6
NO
4
C
5
NC
3
NO
1
C
2
Inverted operation mode
RELA
Y 2
RELA
Y 1
2x M16x1.5
Ethernet
Modbus TCP
1
2
3
4
5
n.c.
GND Output
OUT 2
n.c.
OUT 1
Analogue output
1
3
neutral wire
(N)
n.c.
phase
(L1)
n.c.
Power supply 100 - 240 V AC
for polycarbonate enclosure
Analogue
output
Modbus RTU
(only with
order code J3)
Power supply
100...240 V AC
Power analogue output
Plug
Modbus RTU
Socket
Power analogue output
Plug
Modbus RTU
Socket
Standard
Option E4
Option E5
Option AM3
Power
analogue output
Power
analogue output
1 x M16x1.5 mounted
1 x M16x1.5 enclosed
M16x1.5
Modbus RTU
Digital RS485
Interface
Analogue
output
Modbus RTU
(only with
order code J3)
Power supply
100...240 V AC
EE310/EE360 - Electrical connection for stainless steel housing (HS2)
Option E6
Option AM2
2x M16x1.5
Fig. 34 Polycarbonate enclosure
Fig. 35 Stainless steel enclosure
1
3
Neutral (N)
N.c.
Phase (L1)
N.c.
Power supply 100 - 240 V AC
for polycarbonate enclosure
Plug, 4 poles
front view
2
4
1
3
Neutral wire
(N)
Phase
(L1)
Power supply 100 - 240 V AC
for stainless steel enclosure
Plug, 3 poles
front view
2
Grounding
(PE)
1
2
3
Neutral (N)
Ground (PE)
Phase (L1)
Power supply 100 - 240 V AC
for stainless steel enclosure
Plug, 3 poles
front view
Fig. 36 Plug for power supply 100 - 240 V AC on
polycarbonate enclosure
Fig. 37 Plug for power supply 100 - 240 V AC on
stainless steel enclosure
WARNING
Non-compliance to the following instructions can cause an electrict stroke with the risk of serous injury or death.
▪.
The AM3 option includes a 1.25 A fuse on the 100 - 240 V side. This fuse may not be replaced by the
user, only by the E+E after sales service.
▪.
The protection of the supply cable against excess current and short-circuit must be designated to a wire
cross section of 0.8 mm
2
(AWG 18) (6A fuse).
▪.
The metal enclosure must be grounded during operation.
▪.
All national regulations for installation shall be observed!
NOTICE
External diameter of the supply cable for option AM3: 10...12 mm (0.39...0.47").
Maximum wire cross section for AM3 connecting cable: 1.5 mm
2
(AWG 16) .
External diameter of the cable for Modbus RTU and analogue output female plug: 4...6 mm (0.16...0.24").
Maximal wire cross section for connecting cable: 0.5 mm
2
(AWG 21).