Operating instructions for EE310 Humidity / Temperature Transmitter

Parity

None

Odd

Even

Baudrate

value

value

value

Stop bits

Address

Menu

Modbus  

settings*

* Menu only available with connected Modbus RTU module during EE310 start-up.

Data transmission

Factory settings

Selectable values

Baud rate

9600

300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 76800 

Data bits

8

8

Parity

EVEN

None, odd, even

Stop bits

1

1 or 2

Slave address

231

1...247

The recommended setting for multiple devices in a Modbus RTU network is 9600 8 Even 1. 

Modbus Map

Register

[DEC]

Protocol 

address [HEX]

Measured value

Unit

Type

Read registers: function code 0x03 / 0x04

31021

3FC

Relative humidity

%

32-bit float

31003

3EA

Temperature

°C

32-bit float

31005

3EC

Temperature

°F

32-bit float

31105

450

Dew point temperature

°C

32-bit float

31107

452

Dew point temperature

°F

32-bit float

31131

46A

Frost point / Dew point temperature

°C

32-bit float

31133

46C

Frost point / Dew point temperature

°F

32-bit float

31113

458

Absolute humidity

g/m

3

32-bit float

31115

45A

Absolute humidity

gr/ft

3

32-bit float

31121

460

Mixing ratio

g/kg

32-bit float

31123

462

Mixing ratio

gr/lb

32-bit float

31109

454

Wet bulb temperature

°C

32-bit float

31111

456

Wet bulb temperature

°F

32-bit float

31125

464

Specific enthalpy

kJ/kg

32-bit float

31129

468

Specific enthalpy

BTU/lb

32-bit float

31127

466

Specific enthalpy

ft lbf/lb

32-bit float

31101

44C

Water vapour partial pressure

mbar

32-bit float

31103

44E

Water vapour partial pressure

psi

32-bit float

31151

47E

Volume concentration

ppm

32-bit float

35001

1388

Air pressure

mbar

32-bit float

Write registers: function code 0x06 for 16-bit and 0x10 (decimal: 16) for 32-bit

0001

0

Slave-ID

/

16-bit integer

5001

1388

Air pressure

mbar

32-bit float

Содержание EE310

Страница 1: ...BA_EE310_e V1 5 Technical data subject to change 194474 Operation manual EE310 Humidity Temperature Transmitter...

Страница 2: ...been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interferenc...

Страница 3: ...2 3 4 Installation of the probe with ball valve set 13 4 Optional modules 15 4 1 Alarm module option AM2 15 4 2 Power supply module option AM3 17 4 3 Modbus RTU module option J3 17 4 4 Pluggable probe...

Страница 4: ...hall be handled as such Do not touch the sensing elements inside the sensing head The replacement of the filter cap shall be done with utmost care not to touch the sensors Installation electrical conn...

Страница 5: ...ultaneously and offers extensive error diagnostics The integrated data logging function saves all measured and calcu lated values to the internal memory The data can be displayed as graph directly on...

Страница 6: ...l modules Fig 2 Modular enclosure 2 2 Models EE310 is available for wall or duct mount as well as with various remote probes The remote probes can be employed up to 180 C 356 F and 20 bar 300 psi T1 W...

Страница 7: ...ameter 4 2 mm 0 2 not included in the scope of supply 54 2 13 104 4 09 71 2 80 5 1 0 20 166 6 54 180 7 09 153 6 02 54 2 13 14 0 55 166 6 54 5 1 0 20 7 0 28 Fig 4 Dimensions and mounting template of po...

Страница 8: ...nds analogue range and scaling are freely selectable All settings can be performed via display and push buttons or using the EE PCS Product Configuration Software Error indication The analogue outputs...

Страница 9: ...GND RS485 shielded RS485 A D n c Modbus RTU n c 2 1 4 3 5 RS485 B D GND RS485 shielded RS485 A D n c n c 2 1 4 3 5 RS485 B D GND RS485 shielded RS485 A D n c Modbus RTU n c Fig 7 Plug options for EE3...

Страница 10: ...122 F with display The transmitter shall be mounted with the probe pointing downwards 166 6 54 54 2 13 Fig 8 Mounting of model EE310 T1 3 3 2 T2 Duct mounting EE310 T2 are duct mount transmitters For...

Страница 11: ...sure ment to avoid T gradients along the probe In case of large T difference between the two sides of the separation wall it is highly recommended to insert the probe completely up to the cable outlet...

Страница 12: ...0 T10 may be performed by qualified staff only Special attention shall be paid to the correct installation of the probe into the process In case of inappropriate installation there is the risk for the...

Страница 13: ...wo metal sealing rings see Fig 13 Installation of the probe by utilizing the ball valve set shall be replaced every time prior to re installing the probe The temperature during probe installation may...

Страница 14: ...the ball valve set Removing the probe Hold firmly the probe to avoid it being suddenly expulsed when releasing the lock not May sure nut to bend and damage the probe cable Loosen slowly the lock nut...

Страница 15: ...ilable including hysteresis window and error indication NO NC C NC 6 NO 4 C 5 NC 3 NO 1 C 2 NO NC C Standard Inverted REL 1 REL 2 RELAY 2 RELAY 1 Fig 14 Alarm module option AM2 When error indication m...

Страница 16: ...itching point Switching point Hysteresis Standard Inverted Normal state Switch window Measurand Switching point low Switching point Hysteresis Switching point high Switching point Hysteresis Standard...

Страница 17: ...y by the E E Service National regulations for installation shall be observed 4 3 Modbus RTU module option J3 Instructions for Modbus Protocol Setup please see Application Note AN0103 www epluse com EE...

Страница 18: ...t temperature C 32 bit float 31107 452 Dew point temperature F 32 bit float 31131 46A Frost point Dew point temperature C 32 bit float 31133 46C Frost point Dew point temperature F 32 bit float 31113...

Страница 19: ...on Software or via display and push buttons Working pressure Probe replacement Parameters Humidity coefficient Resistance R0 Capacity C76 Capacity gain Capacity offset Temperature coefficient TK Resis...

Страница 20: ...Remove the blind cover and plug in the USB cable PCB LED 1 LED 2 LED 4 LED 3 Current output Error LED error LED on error category 1 error LED flashes error category 2 Voltage output power supply main...

Страница 21: ...min 15 min 30 min 1 h 5 h 12 h The data logger menu is also used to select the logged data to be shown as a graph as well as for scaling the graph Menu Sampling rate Data logging Axis 1 Measurand Axis...

Страница 22: ...sition Fig 24 Data logging Each point in the graph represents a logged value The points are connected by a linear interpolation One point The data logging continues even when the data memory is full n...

Страница 23: ...ds scaling error indication relay configuration mode set points state adjustment 1 and 2 point humidity temperature adjustment reset to factory adjustment calibration status configuration of Modbus da...

Страница 24: ...ble with 0 1 V output Tab 2 Overview of error codes Error category 1 non critical error can be solved by the user The display blinks and the buzzer beeps every 10 seconds The red status LED flashes Er...

Страница 25: ...ve humidity sensing element can be replaced by the user against an E E replacement sensor see chapter 8 Replacement parts Accessories Sensor replacement procedure Switch off supply voltage Remove the...

Страница 26: ...er Depending on the level of accuracy required the humidity reference can be Humidity Calibrator e g Humor 20 please see www epluse com humor20 Handheld device e g Omniport30 please see www epluse com...

Страница 27: ...iguration changes see user guide at www epluse com relabeling all versions Mating plug for integrated power supply AM3 Mating plug RKC 5 7 AM3 E4 E7 E12 Mating plug RSC 5 7 2 pcs for option E12 E5 E7...

Страница 28: ...0 60 Hz with option AM3 3 Current consumption 2x voltage output for 24V DC AC typ 40 mA 2x current output typ 80 mA Pressure range for pressure tight probe 0 01 20 bar 0 15 300 psi Probe material stai...

Страница 29: ...1 Measurand Axis 2 Measurand Scale maximum value value Scale minimum OFF 1 s 10 s 1 min 5 min 15 min 30 min 1 h 5 h 12 h Delete saved values OFF Temperature C Temperature F Temperature K Rel humidity...

Страница 30: ...t K Frost point K Volume concentr ppm Mode Current Voltage ON Output number Output 1 Output 2 OFF Measurand min max value OK value Cancel Analog range Scaling Error indication OFF Temperature C Temper...

Страница 31: ...ing system Working pressure Probe replacement Parameters Humidity coefficient Resistance R0 Capacity C76 Capacity gain Capacity offset Temperature coefficient TK Resistance Offset Code Daylight saving...

Страница 32: ...steresis Standard Inverted Normal state Error indication Standard Inverted Normal state OFF Temperature C Temperature F Temperature K Rel humidity Vap p pressure mbar Vap p pressure psi Dew point C De...

Страница 33: ...33 Operating instructions for EE310 Humidity Temperature Transmitter 11 Notes...

Страница 34: ...34 Operating instructions for EE310 Humidity Temperature Transmitter...

Страница 35: ...35 Operating instructions for EE310 Humidity Temperature Transmitter...

Страница 36: ...cn BEIJING Tel 86 10 84992361 info epluse cn SHANGHAI Tel 86 21 61176129 info epluse cn E E GERMANY www epluse de Tel 49 6172 13881 0 info epluse de E E FRANCE www epluse fr Tel 33 4 7472 35 82 info...

Отзывы: