Operating manual EE211 Heated humidity and temperature sensor
7 Technical Data
Measurands
Relative Humidity (RH)
Sensor
E+E Sensor HCT01-00D, protected by E+E proprietary coating
Working range
0...100 % RH
RH accuracy
1)
(incl. hysteresis,
non-linearity and repeatability)
±(1.3 + 0.007*measured value) % RH
-5...30 °C
(23...86 °F)
Temperature (T)
Sensor
Pt1000 (tolerance class A, DIN EN 60751)
T-accuracy
±
∆
°C
°C
(at 20 °C (68 °F) : ±0,1 °C)
Outputs
Analogue output
0-5 V / 0-10 V
-1 mA < I
L
< 1 mA
I
L
= load current
(RH: 0...100 %; T: see ordering guide)
0-20 mA / 4-20 mA (3-wire) R
L
≤ 500 Ohm
R
L
= load resistor
Digital interface
RS485, Modbus RTU, max. 32 unit load devices in one bus
General
Power supply (Class III)
15 - 35 V DC
2)
or 24 V AC ±20 %
Current consumption at 24 V
Display
1, 2 or 3 lines, user configurable, with backlight
Connection
Screw terminals, max. 1.5 mm
2
Enclsoure material
Polycarbonate, UL94V-0 (with Display UL94HB) approved
T-probe material
Stainless steel 1.4571
Protection class
IP65 / NEMA 4
Cable gland
M20 x 1.5
Electromagnetic compatibility
EN61326-1
(Industrial Environment)
EN61326-2-3
Temperature range
Operation / Storage: -40...60 °C
(-40...140 °F)
Temperature range with display
Operation:
-20...50 °C
(-4...122 °F)
Storage:
-20...60 °C
(-4...140 °F)
1) Traceable to intern. standards, administrated by NIST, PTB, BEV,...
The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor k=2 (2-times standard deviation).
The accuracy was calculated in accordance with EA-4/02 and with regard to GUM (Guide to the Expression of Uncertainty in Measurement).
2) USA & Canada: class 2 supply required, max. supply voltage 30V
AC
DC
without Display
with Display
without Display
with Display
Voltage ouput
max.
38 mA
rms
max.
49 mA
rms
max.
13 mA
max.
19 mA
Current ouput
typ.
75 mA
rms
typ.
85 mA
rms
max.
34 mA
max.
40 mA
Digital interface typ.
23 mA
rms
typ.
40 mA
rms
typ.
8 mA
typ.
17 mA